Planning the electrical installation
72
*
manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level, check with the motor
manufacturer if additional output filters are needed in the applied drive operation range.
Note 1:
The abbreviations used in the table are defined below.
Explosion-safe (EX) motors
Consult the motor manufacturer regarding the construction of the motor insulation and additional
requirements for explosion-safe (EX) motors.
N
O
N
-
A
B
B
Random-
wound and
form-wound
U
N
< 420 V
Standard:
Û
LL
=
1300 V
-
+ N or CMF
+ N + CMF
420 V <
U
N
< 500 V Standard:
Û
LL
=
1300 V
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced:
Û
LL
=
1600 V, 0.2
microsecond rise
time
-
+ N or CMF
+ N + CMF
500 V <
U
N
< 600 V Reinforced:
Û
LL
=
1600 V
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced:
Û
LL
=
1800 V
-
+ N or CMF
+ N + CMF
600 V <
U
N
< 690 V Reinforced:
Û
LL
=
1800 V
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
Reinforced:
Û
LL
=
2000 V, 0.3
microsecond rise
time ***
-
N + CMF
N + CMF
Abbreviation
Definition
U
N
Nominal voltage of the supply network
Û
LL
Peak line-to-line voltage at motor terminals which the motor insulation must withstand
P
N
Motor nominal power
du/dt
du/dt filter at the output of the drive +E205
CMF
Common mode E208
N
N-end bearing: insulated motor non-drive end bearing
n.a.
Motors of this power range are not available as standard units. Consult the motor
manufacturer.
M
a
nuf
ac
tu
re
r
Motor type
Nominal AC line
voltage
Requirement for
Motor insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size > IEC 315
P
N
> 350 kW
or
frame size > IEC 400
P
N
< 134 hp
and frame size <
NEMA 500
134 hp <
P
N
< 469 hp
or frame size >
NEMA 500
P
N
> 469 hp
or frame size >
NEMA 580
Summary of Contents for ACS800-17LC
Page 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Page 4: ......
Page 10: ...Update notice 6 ...
Page 18: ...Table of contents 12 ...
Page 26: ...Safety instructions 20 ...
Page 32: ...Introduction to the manual 26 ...
Page 60: ...Hardware description 54 ...
Page 74: ...Mechanical installation 68 ...
Page 114: ...Electrical installation 108 ...
Page 142: ...Maintenance 136 ...
Page 150: ...Internal cooling circuit 144 ...
Page 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Page 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Page 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...