Technical data
91
Quick guide for selecting between gG and aR fuses
The table below is a short cut in selecting between gG and aR fuses. The
combinations (cable size, cable length, transformer size and fuse type) in the table
fulfil the minimum requirements for the proper operation of the fuse.
Note 1:
The supply transformer minimum power in kVA is calculated with a z
k
value of 6% and
frequency 50 Hz.
ACS800-04 size
Cable type
Supply transformer minimum apparent power
S
N
(kVA)
Copper
Aluminium
Maximum cable length with gG fuses
Maximum cable length with aR fuses
10 m
50 m
100 m
10 m
100 m
200 m
Three-phase supply voltage 208 V,
220 V,
230 V
or 240 V
-0080-2
3×120 Cu
3×185 Al
120
150
-
81
81
-
-0100-2
3×150 Cu
3×240 Al
140
170
-
96
96
-
-0120-2
3×240 Cu
2 × (3×95) Al
140
170
-
120
120
-
-0140-2
2 × (3×120) Cu 3 × (3×95) Al
250
320
-
160
160
-
-0170-2
2 × (3×120) Cu 3 × (3×95) Al
250
320
-
180
180
-
-0210-2
3 × (3×95) Cu
2 × (3×240) Al
310
400
-
210
230
-
-0230-2
3 × (3×120) Cu 3 × (3×185) Al
310
400
-
240
340
-
-0260-2
3 × (3×150) Cu 3 × (3×240) Al
410
510
-
270
380
-
-0300-2
3 × (3×150) Cu 3 × (3×240) Al
410
510
-
290
380
-
Three-phase supply voltage 380 V,
400 V
or 415 V
-0140-3
3×120 Cu
3×185 Al
200
220
260
160
160
160
-0170-3
3×150 Cu
3×240 Al
240
260
310
170
170
170
-0210-3
3×240 Cu
2 × (3×120) Al
240
260
310
200
200
200
-0260-3
3 × (3×70) Cu
3 × (3×120) Al
430
460
560
310
310
310
-0320-3
3 × (3×95) Cu
2 × (3×240) Al
530
600
750
350
350
440
-0400-3
3 × (3×120) Cu 3 × (3×185) Al
530
600
750
410
470
660
-0440-3
3 × (3×150) Cu 3 × (3×240) Al
700
770
930
470
530
730
-0490-3
3 × (3×150) Cu 3 × (3×240) Al
700
770
930
490
530
730
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or
500
V
-0170-5
3×120 Cu
3×150 Al
250
270
310
200
200
200
-0210-5
3×150 Cu
3×240 Al
290
320
360
220
220
220
-0260-5
3×240 Cu
2 × (3×120) Al
290
320
360
260
260
260
-0320-5
2 × (3×120) Cu 3 × (3×95) Al
530
570
670
370
370
370
-0400-5
2 × (3×150) Cu 2 × (3×240) Al
660
720
840
440
440
480
-0440-5
3 × (3×95) Cu
3 × (3×150) Al
660
720
840
500
570
760
-0490-5
3 × (3×120) Cu 3 × (3×185) Al
660
720
840
520
570
760
-0550-5
2 × (3×240) Cu 3 × (3×240) Al
880
980
1200
580
670
880
-0610-5
3 × (3×150) Cu 3 × (3×240) Al
880
980
1200
610
670
880
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or
690
V
-0140-7
3×70 Cu
3×95 Al
220
220
240
160
160
160
-0170-7
3×95 Cu
3×120 Al
260
260
280
190
190
190
-0210-7
3×120 Cu
3×150 Al
340
360
390
230
230
230
-0260-7
3×150 Cu
3×185 Al
340
360
390
260
260
260
-0320-7
3×240 Cu
2 × (3×120) Al
400
410
430
360
360
360
-0400-7
3×240 Cu
3 x (3×70) Al
550
570
610
400
400
400
-0440-7
2 × (3×120) Cu 2 × (3×150) Al
730
780
860
460
460
460
-0490-7
2 × (3×120) Cu 3 × (3×95) Al
730
780
860
510
510
510
-0550-7
2 × (3×150) Cu 3 × (3×120) Al
730
780
860
560
560
560
-0610-7
3 × (3×95) Cu
3 × (3×150) Al
960
1000
1100
640
640
640
PDM code: 00556489 A