Technical data
84
1)
50% overload is available for one minute every 5 minutes if ambient temperature is less than 25 °C.
If ambient temperature is 40 °C, max. available overload is 37%.
2)
50% overload is available for one minute every 5 minutes if ambient temperature is less than 30 °C.
If ambient temperature is 40 °C, max. available overload is 40%.
3)
50% overload is available one minute every 5 minutes if ambient temperature is less than 20 °C. If
ambient temperature is 40 °C, max. available overload is 30%.
4)
50% overload is available one minute every 5 minutes if ambient temperature is less than 35 °C. If
ambient temperature is 40 °C, max. available overload is 45%.
*
higher value applicable if output frequency is above 41 Hz
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or
500
V
-0170-5
196
326
132
192
132
162
110
R7
540
3000
-0210-5
245
384
160
240
160
192
132
R7
540
3800
-0260-5
289
432
200
284
200
224
160
R7
540
4500
-0320-5
440
588
250
435
250
340
200
R8
1220
6850
-0400-5
515
588
315
510
315
370
250
R8
1220
7800
-0440-5
550
840
355
545
355
490
315
R8
1220
7600
-0490-5
602
840
400
590
400
515
2)
355
R8
1220
8100
-0550-5
684
1017
450
670
450
590
2)
400
R8
1220
9100
-0610-5
718
1017
500
704
500
632
3)
450
R8
1220
9700
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or
690
V
-0140-7
134
190
132
125
110
95
90
R7
540
2800
-0170-7
166
263
160
155
132
131
110
R7
540
3550
-0210-7
166/203* 294
160
165/195* 160
147
132
R7
540
4250
-0260-7
175/230* 326
160/200* 175/212* 160/200* 163
160
R7
540
4800
-0320-7
315
433
315
290
250
216
200
R8
1220
6150
-0400-7
353
548
355
344
315
274
250
R8
1220
6650
-0440-7
396
656
400
387
355
328
315
R8
1220
7400
-0490-7
445
775
450
426
400
387
355
R8
1220
8450
-0550-7
488
853
500
482
450
426
400
R8
1220
8300
-0610-7
560
964
560
537
500
482
450
R8
1220
9750
PDM code: 00096931-G
ACS800-04
size
Nominal ratings
No-
overload
use
Light-overload use Heavy-duty use
Frame
size
Air flow
Heat
dissipation
I
cont.max
A
I
max
A
P
cont.max
kW
I
2N
A
P
N
kW
I
2hd
A
P
hd
kW
m
3
/h
W
Summary of Contents for ACS800-04
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 54: ...Planning the electrical installation 54 ...
Page 72: ...Motor control and I O board RMIO 72 ...
Page 116: ...Resistor braking 116 ...
Page 117: ......