Planning the electrical installation
36
Requirements table
The following table shows how to select the motor insulation system and when an optional ABB du/dt
filter, insulated N-end (non-driven end) motor bearings and ABB common mode filters are required. The
motor manufacturer should be consulted regarding the construction of the motor insulation and
additional requirements for explosion-safe (EX) motors. Failure of the motor to fulfil the following
requirements or improper installation may shorten motor life or damage the motor bearings and voids
the warranty.
Man
u
factu
rer
Motor type
Nominal mains
voltage (AC line
voltage)
Requirement for
Motor insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size > IEC 315
P
N
> 350 kW
or
frame size > IEC 400
P
N
< 134 HP
and frame size <
NEMA 500
134 HP <
P
N
< 469 HP
or frame size >
NEMA 500
P
N
> 469 HP
or frame size >
NEMA 580
A
B
B
Random-
wound M2_
and M3_
U
N
< 500 V
Standard
-
+ N
+ N + CMF
500 V <
U
N
< 600 V Standard
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
or
Reinforced
-
+ N
+ N + CMF
600 V <
U
N
< 690 V Reinforced
+ du/dt
+ du/dt + N
+ du/dt + N + CMF
Form-wound
HX_ and AM_
380 V <
U
N
< 690 V Standard
n.a.
+ N + CMF
P
N
< 500 kW: + N +
CMF
P
N
> 500 kW: + N +
CMF + du/dt
Old* form-
wound HX_
and modular
380 V <
U
N
< 690 V Check with the
motor
manufacturer.
+ du/dt with voltages over 500 V + N + CMF
Random-
wound HX_
and AM_ **
0 V <
U
N
< 500 V
Enamelled wire
with fibre glass
taping
+ N + CMF
500 V <
U
N
< 690 V
+ du/dt + N + CMF
Summary of Contents for ACS800-04