Technical data
100
Prevention of Unexpected Start: AGPS-21 board
Nominal input voltage
115 VAC or 230 VAC
Input voltage range
(selected by jumper)
95...132 VAC (X3 on), 185...265 VAC (X4 on, default)
Nominal frequency
50/60 Hz
Current
0.77 A at 115 V, 0.44 A at 230 V
Max. external fuse
16 A
Input connector X1
3 × 2.5 mm
2
User connector 1, 2, 3
600 V, 25 A, 0.5...4 mm
2
(20...12 AWG)
Output voltage
24 V + 0.5 V
Nominal output current
1.7 A (50 °C, 122 °F)
X2 terminal block type
JST B3P-VH
Ambient temperature
0...50 °C (32...122 °F)
Relative humidity
30...90%, no condensation allowed
Approvals
CE, C-UL US listed
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 4000 m (13123 ft) above
sea level [above 1000 m
(3281 ft), see section
-
-
Air temperature
-15 to +50 °C (5 to 122 °F).
-40 to +70 °C (-40 to
+158 °F)
-40 to +70 °C (-40 to
+158 °F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC 60721-3-3, IEC 60721-3-
2, IEC 60721-3-1)
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
(IEC 60068-2)
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 to 200 Hz) sinusoidal
Shock
(IEC 60068-2-29)
Not allowed
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Free fall
Not allowed
100 mm (4 in.) for weight
over 100 kg (220 lb)
100 mm (4 in.) for weight
over 100 kg (220 lb)
Summary of Contents for ACS800-04
Page 4: ......
Page 12: ...Safety instructions 12 ...
Page 54: ...Planning the electrical installation 54 ...
Page 72: ...Motor control and I O board RMIO 72 ...
Page 116: ...Resistor braking 116 ...
Page 117: ......