Technical data
88
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or
500
V
-0170-5
191
3820
250
550 000
500
ABB Control
OFAF1H250
1
-0210-5
243
4510
315
1 100 000
500
ABB Control
OFAF2H315
2
-0260-5
291
4510
315
1 100 000
500
ABB Control
OFAF2H315
2
-0320-5
424
8280
500
2 900 000
500
ABB Control
OFAF3H500
3
-0400-5
498
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0440-5
543
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0490-5
590
10200
630
4 000 000
500
ABB Control
OFAF3H630
3
-0550-5
669
13500
800
7 400 000
500
ABB Control
OFAF3H800
3
-0610-5
702
13500
800
7 400 000
500
ABB Control
OFAF3H800
3
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or
690
V
-0140-7
126
2400
160
220 000
690
ABB Control
OFAA1GG160
1
-0170-7
156
2850
200
350 000
690
ABB Control
OFAA1GG200
1
-0210-7
191
3820
250
700 000
690
ABB Control
OFAA2GG250
2
-0260-7
217
3820
250
700 000
690
ABB Control
OFAA2GG250
2
-0320-7
298
4510
315
820 000
690
ABB Control
OFAA2GG315
2
-0400-7
333
6180
400
1 300 000
690
ABB Control
OFAA3GG400
3
-0440-7
377
8280
500
3 800 000
690
ABB Control
OFAA3H500
3
-0490-7
423
8280
500
3 800 000
690
ABB Control
OFAA3H500
3
-0550-7
468
8280
500
3 800 000
690
ABB Control
OFAA3H500
3
-0610-7
533
10800
630
10 000 000
690
Bussmann
630NH3G-690 **
3
** rated breaking capacity only up to 50 kA
1)
minimum short-circuit current of the installation
Note 1:
Planning the electrical installation
:
Thermal overload and short-circuit protection
. For UL
on page
.
Note 2:
In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3:
Larger fuses than the recommended ones must not be used.
Note 4:
Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.
PDM code: 00096931-G, 00556489 A
gG fuses
ACS800-04
size
Input
current
Min. short-
circuit
current
1)
Fuse
A
A
A
A
2
s
V
Manufacturer
Type
IEC size
Summary of Contents for ACS800-04