Checking the installation
116
3
Busbars
3.1
The types (Al/Cu) and cross-sections of busbars are correct.
3.2
Busbars are intact and joint surfaces are clean. There are no metal scraps on the busbars that could
cause a short-circuit.
3.3
The placement and mounting of busbars is correct.
3.4
The electrical connection of busbars.
Check that the surfaces in electrical connections of aluminium
and uncoated busbars are rubbed. Check that anti-oxidant joint compound is used in electrical
connections of aluminium busbars. Check that the number of washers and the sizes of bolts are
correct.
3.5
Busbar supports and lead-in insulators are visually intact and degreased, and placed and mounted
correctly.
3.6
The electrical connections on the main circuit are tightened to required torque and marked with a
green marking.
4
Cabling and wiring
4.1
Wiring of the main circuit. Check
• AC supply input
• AC output
• supply for brake resistor (if used).
4.2
Wiring of the 230 VAC circuit. Check
• terminal strips and relays
• supply of cabinet fans (if used)
• 24 VDC auxiliary voltage circuit (optional module supply)
• supply for cooling fan of the braking resistor(s) (if used).
4.3
Wiring of the converter module circuit. Check
• RDCU module (RMIO board) connections
• control cable connections
• control panel cable connections.
4.4
Cable types, cross-sections, colours and optional markings are correct.
4.5
Check the cabling for circuits susceptible to interference. Check the twisting of cables and cable
routes.
4.6
Check that cables without short-circuit protection
• can carry the load current
• are shorter than 3 m (10 ft)
• are assembled separate to other cables
• are protected by an enclosure or duct.
4.7
Cable connectors and fibre optic cables are intact and according to instructions. Check the termination
of cables (e.g. AMP connectors), the crimping of cable lugs and ferrules. Check that the connectors
are suitable for the cables and the correct crimping tool has been used.
Check that
• insulation of the cable is not underneath the connector
• all strands of the cable are inside the connector
• connector is not broken
• cable is deep enough in its connector.
Step
Check item
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......