Cabinet cooling data
IP 22 cabinet with no extra fan
The table below shows the data the IP 22 cabinet should meet to ensure efficient
cooling of the converter module. No extra fan is used. The pressure drop over the
cabinet is the additional counterpressure that the module fan is capable of
overcoming while still maintaining the required air flow through the module.
* size when the outlet is located on the cabinet roof
IP 54 cabinet with an extra fan
The table below shows the data the IP 54 cabinet should meet to ensure efficient
cooling of the converter module. An extra fan is used. The pressure drop over the
cabinet is the counterpressure the extra fan must overcome. The given fan types
and filter materials are examples. Corresponding products by another manufacturer
may be used as well. See the manufacturer’s Internet site for the detailed
specification.
* inlet filter 50 % unclean
Frame
size
Temp. rise
Pressure drop
Cabinet air inlet
Min. cabinet air
outlet size*
Over module
Over module
Over cabinet
Min. size
Filter
°C
Pa
Pa
mm
by Luftfilter
mm
R7
30
300
30
288×292+688×521
airTex G150
398×312 (2 pcs)
R8
30
300
45
288×292+688×521
airTex G150
398×312 (2 pcs)
00096931
Frame
Size
Temp. rise
Pressure drop
Extra fan type
Air inlet and outlet filter by Luftfilter
Over module
Over cabinet
Min. inlet (door)
Min. outlet (roof)
°C
Pa
mm
mm
R7
30
250*
RB2C-225/088 K093 or
R2E225-AU64 by ebm
airComp 300-50
288×292 + 688×521
airTex G150
398×312 (2 pcs)
R8
30
250*
RH35M-4EK.2F.1R by
Ziehl-Abegg or RB4T-
355/170 by ebm
airComp 300-50
288×292 + 688×521
airTex G150
398×312 (2 pcs)
00096931
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......