Checking the installation
118
Labels, switches, fuses and doors
Checks for labels, switches, fuses and doors are listed below.
Step
Check item
7
Labels
7.1
The name plates are correct. The name plates are located correctly. Check the name plates for
• cabinet
• main circuit fuses
• settings of the circuit-breakers
• safety switches of the main circuit.
7.2
The warning and instruction stickers are located correctly.
Stickers required inside the cabinet:
•
near all grounding connections
• inside the cabinet door main fuse specification label, fuse installation (centring) note
•
on contact covers
• warning of live terminals of a blown fuse on contact cover on the main fuses
• warning about apparatus not disconnected from the supply network by the main switch on contact covers of
these busbars and apparatus
• warning sticker for residual voltages of the converter capacitor banks placed on the converter module.
Stickers required on the cabinet door:
• five-minute warning of residual voltage
•
• sticker on the control panel mounting platform (if used)
• emergency stop and start switch label (if applicable)
• main switch label.
8.
Switches, fuses and doors
8.1
Check the functioning of mechanical switches by closing and opening them.
8.2
Check that fuses can be changed with a fuse handle. Check that fuse disconnectors and sockets match each
other.
8.3
Check the appropriate length and fastening of the operation rod of the main disconnecting switch.
When switch fuses or disconnecting switches are closed, the corresponding cabinet doors cannot be opened:
1. Lock the cabinet door with the main switch in OPEN position (0).
2. Close the main switch (position 1).
3. Unlock the door. It must not be possible to open the door by pulling the handle.
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......