Planning the cabinet installation
34
Drive module of frame size R7 on its back
Support the module from below.
The fastening points are not
sturdy enough to carry the
weight of the module when laid
on its back.
Leave space above the module
for maintenance
Air baffle for preventing cooling
air recirculation
Ensure that the cooling air will flow freely and
is clean. Use filter mats if the input cooling air
is taken near the floor surface and contains
dust.
Prevent dripping water from
entering the drive module.
64796003_bottom_exit_copy<64796003>.asm
Note:
Air inlet into the drive module
goes through the front gratings of
the module. Do not cover them.
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......