Checking the installation
117
Groundings and protection
Checks for groundings and protections are listed below. Tips for installations where
EMC emissions must be minimised are given in column
Extra requirements for EMC
.
4.8
Connection of cables to devices and terminal blocks. Check that
• cables are connected to terminals tight enough by pulling the cable
• cable termination on terminals chaining is done correctly
• bare conductors are not too far outside the terminal causing an insufficient clearance or loss of
shielding against contact.
4.9
Cables are not lying against sharp edges or bare live parts. Bending radius of fibre optic cables at least
3.5 cm (1.38 in.).
4.10
The type, markings, insulation plates and cross connections of terminal blocks are correct.
5.
Clearances and creepage distances
5.1
Clearances outside the modules are at least 12.7 mm (0.5 in.).
5.2
Creepage distances outside the modules are at least 12.7 mm (0.5 in.).
Step
Check item
Extra requirements for EMC
6
Groundings and protection
6.1
The grounding colours, cross-section and grounding points
of modules and other equipment match the circuit diagrams.
No long routes for pigtails
6.2
Connections of PE cables and busbars are tight enough.
Pull the cable to test that it does not loosen.
No long routes for pigtails
6.3
Doors equipped with electrical equipment are grounded.
No long grounding routes. From EMC standpoint
best result is achieved with a flat copper braid.
6.4
Fans that can be touched are shrouded.
6.5
Live parts inside the doors are protected against direct
contact to at least IP 2x (if required).
Step
Check item
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......