Planning the cabinet installation
36
360° high frequency grounding of the control cable shields is recommended at their
entries. The shields can be grounded by means of conductive shielding cushions
pressed against the cable shield from both directions:
Grounding of cable shields
* required for motor cables in first environment installations. First environment EMC compliance is
defined in chapter
Technical data
/
CE marking
in
ACS800-04/04M/U4 Hardware Manual
[64671006
(English)].
Installing the Drive Control Unit (RDCU)
See
RDCU Drive Control Unit Hardware Manual
[3AFE64636324 (English)].
Shielding cushion
(conductive)
Cable
Cable grommet
Bare cable shield
Cabinet bottom plate
EMC sleeve *
Lead-through plate
Strip this part of
the cable
Cable shield
Base plate
PE terminal of the
cabinet or drive module
Strain relief
Recommended for
control cables
To power terminals
Example cable lead-through
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......