Mechanical installation of non-pre-assembled units (ACS800-04M)
112
WARNING!
Fasten the output
busbars to the insulating supports
with
M8x16
screws when no cable
lug terminal is connected, but with
M8x20 screws when a cable lug
terminal is connected as well.
Screwing an M8x20 screw without
a cable lug terminal through the
busbar into the insulating support
will break the insulating support.
7
8 M8. Use the side plate fastening screw
for fastening the PE terminal by side.
M10
M8x20
Frame size R7 +H360: AC, DC and brake busbars connected (+H356 included)
5
M10
PE
M8x16
M8x16
M10x25
6
M10x25
5
Tightening torque
M8: 15...22 Nm (3.7 lbf ft)
M10: 30...44 Nm (22...32 lbf ft)
M10x25
Summary of Contents for ACS 800 Series
Page 4: ......
Page 10: ...Table of contents 10...
Page 119: ...Dimensional drawings 119 Dimensional drawings...
Page 120: ...Dimensional drawings 120 Frame size R7 without pedestal mm 64796003_3 7 E Center of gravity...
Page 121: ...Dimensional drawings 121 Frame size R7 with bottom exit mm 64796003_6 7 G...
Page 123: ...Dimensional drawings 123 Frame size R7 with busbars on the left side mm 64796003_5 7 G...
Page 127: ...Dimensional drawings 127 Frame size R8 without pedestal mm 64801082_3 6 E Center of gravity...
Page 128: ...Dimensional drawings 128 Frame size R8 with busbars on the left side mm 64801082_5 6 E...
Page 136: ...Dimensional drawings 136 Control Panel Holder RPMP 21 J413 64770306_20 20 E...
Page 138: ...Dimensional drawings 138 Dimensional drawings USA...
Page 140: ...Dimensional drawings 140 Frame size R7 with bottom exit inches 68439221_6 7 F F F...
Page 142: ...Dimensional drawings 142 Frame size R7 with busbars on the left side inches 68439221_5 7 F...
Page 152: ...Dimensional drawings 152...
Page 160: ...Assembly drawings 160...
Page 161: ......