Default control connections of ABB standard macro
■
Connection diagram
EN - Quick installation and start-up guide 17
EN
ES
PL
TR
ZH
Default I/O connections (ABB standard macro)
X1
Reference voltage and analog inputs
1
SCR
Signal cable shield (screen)
2
AI1
Open for configuration
1)
3
AGND
Analog input circuit, common
4
+10V
10 V DC reference voltage
5
AI2
Open for configuration
2)
6
AGND
Analog input circuit, common
7
AO1
Output frequency, 0…20
mA
9)
8
AO2
Motor current
9)
9
AGND
Analog output circuit common
X2, X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 VDC, max. 250 mA
3)
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Start (0) /Stop (1)
8)
14
DI2
Open for configuration
15
DI3
Open for configuration
16
DI4
Open for configuration
17
DI5
Open for configuration
18
DI6
Open for configuration
X6, X7, X8 Relay outputs
19
RO1C
Ready Run
9)
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
9)
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
9)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
B+
Internal Modbus RTU (EIA-485)
30
A-
31
DGND
(Frame R0~R2)
S100
TERM&BIAS
Termination resistor and bias resistor switch
(Frame R3~R8)
S100
TERM
Termination resistor switch
S200
BIAS
Bias resistor switch
X4
Safety torque off
R0~R2
R3~R8
33
-
OUT1
Safety torque off function. Factory connection.
Both circuits must be closed for the drive to
start. See
Safe torque off function
.
34
SGND
OUT2
35
OUT1
SGND
36
IN1
IN1
37
IN2
IN2
X10
24 V AC/DC (frames R6~R8 only)
40
24 V AC/DC- in
24V AC/DC input, for control unit power supply
when external main power is disconnected.
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output (frames R0~R2 only)
42
+24 V
Aux. voltage 24 V DC, max. 250 mA
3)
43
DGND
Aux. voltage output common
44
DCOM
Digital input common for all
4)
6)
Max.
500 ohm
7 )
1…10 kohm
R3~R8
4)
5)
Terminal sizes
•
(frames R0…R8): 0.14…1.5 mm
2
(all terminals)
Electrical installation 85
11
Summary of Contents for ACQ80-04 Series
Page 1: ...ABB DRIVES FOR WATER ACQ80 04 drives 0 75 to 160 kW 1 0 to 215 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 18: ...18...
Page 24: ...24...
Page 38: ...38...
Page 50: ...50...
Page 64: ...64...
Page 98: ...98...
Page 110: ...110...
Page 140: ...Frame R3 IP20 140 Dimension drawings...
Page 146: ...146...
Page 162: ...162...
Page 168: ......