Operation principle
1.
The Safe torque off activates (the activation switch is opened, or safety relay contacts
open).
2.
The STO inputs of the drive control board de-energize.
3.
The control board cuts off the control voltage from the output IGBTs.
4.
The control program generates an indication as defined by parameter
31.22
(refer to
the firmware manual of the drive).
The parameter selects which indications are given when one or both STO signals are
switched off or lost. The indications also depend on whether the drive is running or
stopped when this occurs.
Note:
This parameter does not affect the operation of the STO function itself. The STO function
will operate regardless of the setting of this parameter: a running drive will stop upon
removal of one or both STO signals, and will not start until both STO signals are restored
and all faults reset.
Note:
The loss of only one STO signal always generates a fault as it is interpreted as a
malfunction of STO hardware or wiring.
5.
The motor coasts to a stop (if running). The drive cannot restart while the activation
switch or safety relay contacts are open. After the contacts close, a reset may be needed
(depending on the setting of parameter
31.22
). A new start command is required to start
the drive.
154 The Safe torque off function
Summary of Contents for ACQ80-04 Series
Page 1: ...ABB DRIVES FOR WATER ACQ80 04 drives 0 75 to 160 kW 1 0 to 215 hp Hardware manual...
Page 2: ......
Page 4: ......
Page 18: ...18...
Page 24: ...24...
Page 38: ...38...
Page 50: ...50...
Page 64: ...64...
Page 98: ...98...
Page 110: ...110...
Page 140: ...Frame R3 IP20 140 Dimension drawings...
Page 146: ...146...
Page 162: ...162...
Page 168: ......