Fault tracing 209
Fault messages
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
1080
Backup/Restore
timeout
Panel or PC tool has failed to
communicate with the drive
when backup was being made
or restored.
Request backup or restore again.
1081
Rating ID fault
Drive software is not able to
read the rating ID of the drive.
Reset the fault to make the drive try to
reread the rating ID.
If the fault reappears, cycle the power to
the drive. You may have to be repeat this.
If the fault persists, contact your local
ABB representative.
2281
Calibration
Measured offset of output
phase current measurement or
difference between output
phase U2 and W2 current
measurement is too great (the
values are updated during
current calibration).
Try performing the current calibration
again.
If the fault persists, contact your local
ABB representative.
2310
Overcurrent
Output current has exceeded
internal fault limit.
In addition to an actual
overcurrent situation, this fault
may also be caused by an
earth fault or supply phase
loss.
Check motor load.
Check acceleration times in parameter
group
(speed
(frequency control). Also check
parameter
Check motor and motor cable (including
phasing and delta/star connection).
Check there are no contactors opening
and closing in motor cable.
Check that the start-up data in parameter
group 99 corresponds to the motor rating
plate.
Check that there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
See chapter
Electrical installation
,
section
Checking the insulation of the
assembly
in the
Hardware manual
of the
drive.
2330
Earth leakage
Programmable fault:
Drive has detected load
unbalance typically due to
earth fault in motor or motor
cable.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
.)
If no earth fault can be detected, contact
your local ABB representative.
ACQ80 FW.book Page 209 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...