![ABB ACQ80-04 Series Firmware Manual Download Page 254](http://html.mh-extra.com/html/abb/acq80-04-series/acq80-04-series_firmware-manual_2932254.webp)
254 Fieldbus control through a fieldbus adapter
5
Ramp hold
1
ramp function.
Proceed to
RAMP FUNCTION GENERATOR: ACCELERATOR D
.
0
Halt ramping (Ramp Function Generator output held).
6
Ramp in zero
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface is set as the
source for this signal by drive parameters.
0
Force Ramp function generator input to zero.
7
Reset
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-ON
INHIBITED
.
Note:
This bit is effective only if the fieldbus interface is set as the
source of the reset signal by drive parameters.
0
Continue normal operation.
8
Inching 1
1
Accelerate to inching (jogging) setpoint 1.
Notes:
• Bits 4…6 must be 0.
• See also section
Parameter 97.01 Switching frequency reference
and 97.02 Minimum switching frequency (page 162).
).
0
Inching (jogging) 1 disabled.
8
Reserved
9
Inching 2
1
Accelerate to inching (jogging) setpoint 2.
See notes at bit 8.
0
Inching (jogging) 2 disabled.
9
Reserved
10
Remote cmd
1
Fieldbus control d.
0
Control word and reference not getting through to the drive, except
for bits 0…2.
11
Ext ctrl loc
1
Select External Control Location EXT2. Effective if control location is
parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control location is
parameterized to be selected from fieldbus.
12
User bit 0
1
User configurable
0
13
User bit 1
1
0
14
User bit 2
1
0
15
User bit 3
1
0
Bit
Name
Value STATE/Description
ACQ80 FW.book Page 254 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...