58 Control macros
Default control connections for the ABB standard macro
X1
Reference voltage and analog inputs
1
SCR
Signal cable shield (screen)
2
AI1
Open for configuration
1)
3
AGND
Analog input circuit, common
4
+10V
10 V DC reference voltage
5
AI2
Open for configuration
2)
6
AGND
Analog input circuit, common
7
AO1
Output frequency, 0…20 mA
9)
:
see
8
AO2
Motor current
9)
:
see
9
AGND
Analog output circuit common
X2, X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 VDC, max. 250 mA
3)
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Start (0) /Stop (1) see
14
DI2
Open for configuration
15
DI3
Open for configuration
16
DI4
Open for configuration
17
DI5
Open for configuration
18
DI6
Open for configuration
X6, X7, X8 Relay outputs
19
RO1C
Ready Run
9)
: see
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
9)
: see
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
9)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
B+
Internal Modbus RTU (EIA-485), see
control through the embedded fieldbus
30
A-
31
DGND
(Frame R0~R2)
S100
TERM&BIAS
Termination resistor and bias resistor switch
(Frame R3~R8)
S100
TERM
Termination resistor switch
S200
BIAS
Bias resistor switch
X4
Safety torque off
R0~R2
R3~R8
33
-
OUT1
Safety torque off function. Factory connection.
Both circuits must be closed for the drive to
start. See
Safe torque off function
in the drive
hardware
manual.
34
SGND
OUT2
35
OUT1
SGND
36
IN1
IN1
37
IN2
IN2
X10
24 V AC/DC (frames R6~R8 only)
40
24 V AC/DC- in
24V AC/DC input, for control unit power supply
when external main power is disconnected.
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output (frames R0~R2 only)
42
+24 V
Aux. voltage 24 V DC, max. 250 mA
3)
43
DGND
Aux. voltage output common
44
DCOM
Digital input common for all
4)
6)
Max.
500 ohm
7 )
1…10 kohm
R3~R8
4)
5)
ACQ80 FW.book Page 58 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...