Fault tracing 213
5696
PU state feedback
State feedback from output
phases does not match control
signals.
Contact your local ABB representative.
5697
Charging feedback
Charging feedback signal
missing.
Check the feedback signal coming from
the charging system
5698
Unknown PU fault
The power unit logic generated
a fault which is not known by
software.
Check the logic and software
compatibility.
50A0
Fan
Cooling fan stuck or
disconnected.
Check fan operation and connection.
Replace fan if faulty.
6181
FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6306
FBA A mapping file
Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6481
Task overload
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
6487
Stack overflow
Internal fault.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
64A1
Internal file load
File read error.
Reboot the control unit (using parameter
) or by cycling
power. If the problem persists, contact
your local ABB representative
64A3
Application loading
Application file incompatible or
corrupted.
Check the auxiliary code. See actions for
each code below.
8006 Not enough memory for the
application.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated by
Automation Builder.
8007 The application contains the
wrong system library version.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
8008 The application is empty.
In Automation Builder, give a “Clean”
command and reload the application.
8009 The application contains
invalid tasks.
In Automation Builder, check application
task configuration, give a “Clean all”
command, and reload the application.
800A The application contains an
unknown target (system)
library function.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated by
Automation Builder.
64A4
Rating ID fault
Rating ID load error.
Contact ABB.
64A6
Adaptive program
Fault in adaptive program.
Check the fault code extension.
Code
(hex)
Fault / Aux. code
(
aux
code visible only on
assistant control panel
and drive composer
)
Cause
What to do
ACQ80 FW.book Page 213 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...