Parameters 123
Estimated
temperature
Estimated motor temperature (see parameter
).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient temperature
of the motor in
1
1 × Pt100 analog
I/O
Pt100 sensor connected to a standard analog input selected
by parameter
output.
The following settings are required:
• Set the hardware jumper or switch related to the analog
input to
U
(voltage). Any change must be validated by a
control unit reboot.
• Set the appropriate analog input unit selection parameter
in group
(volt).
, set the source
selection parameter of the analog output to
.
The analog output feeds a constant current through the
sensor. As the resistance of the sensor increases along with
its temperature, the voltage over the sensor increases. The
voltage is read by the analog input and converted into
degrees.
5
2 × Pt100 analog
I/O
As selection
, but with two sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
6
3 × Pt100 analog
I/O
As selection
, but with three sensors
connected in series. Using multiple sensors improves
measurement accuracy significantly.
7
Direct temperature
The temperature is taken from the source selected by
parameter
. The value of the
source is assumed to be degrees Celsius.
11
Defines the fault limit for temperature supervision function 2.
When measured temperature 1 exceeds the limit, the drive
trips on fault
The unit is selected by parameter
.
130 °C or
266 °F
-60…5000 °C or
-76…9032 °F
Fault limit for temperature monitoring function 2.
1 = 1 unit
Defines the warning limit for temperature supervision
function 2. When measured temperature 1 exceeds the limit,
warning
is generated.
The unit is selected by parameter
.
110 °C or
230 °F
-60…5000 °C or
-76…9032 °F
Warning limit for temperature monitoring function 2.
1 = 1 unit
Specifies the analog input when the setting of
requires measurement through an
analog input.
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value
Analog input AI2 on the control unit.
2
on page
-
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 123 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...