120 Parameters
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 6
exceeds its limits.
Note:
This parameter does not affect the status indicated by
.
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
Drive trips on fault
2
Fault if running
Drive trips on fault
if the motor is
running.
3
Selects the signal to be monitored by signal supervision
function 6.
For the available selections, see parameter
.
Defines a filter time constant for the signal monitored by
signal supervision 6.
0.000 s
0.000 … 30.000 s
Signal filter time.
1000 = 1 s
Defines the lower limit for signal supervision 6.
0.00
-21474836.00…
21474836.00
Low limit.
-
Defines the upper limit for signal supervision 6.
0.00
-21474836.00…
21474836.00
Upper limit.
-
Defines the hysteresis for the signal monitored by signal
supervision 6.
0.00
0.00…100000.00
Hysteresis.
-
35
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section
(page
).
Shows motor temperature as estimated by the internal motor
thermal protection model (see parameters
…
).
The unit is selected by parameter
.
This parameter is read-only.
0
-60…1000 °C or
-76…1832 °F
Estimated motor temperature.
1 = 1°C
Shows temperature received through the source defined by
parameter
. The unit is selected
by parameter
.
Note:
With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter
(excessive
temperature) is shown.
This parameter is read-only.
0
-60…5000 °C or
-76…9032 °F
Measured temperature 1.
1 = 1 unit
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 120 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...