126 Parameters
Defines the thermal time constant for use with the motor
thermal protection model, defined as the time to reach 63% of
the nominal motor temperature. See the motor
manufacturer's recommendations.
256 s
100…10000 s
Motor thermal time constant.
1 = 1 s
Selects how the drive reacts when the motor reaches
overload condition.
No action
None.
0
Warning only
The drive generates an
warning.
1
Warning and fault
The drive generates an
warning and
2
Selects the motor overload class to be used.
Class 5
Class 5 relay trip class
0
Class 10
Class 10 relay trip class
1
Class 20
Class 20 relay trip class
2
Class 30
Class 30 relay trip class
3
Class 40
Class 40 relay trip class
4
No.
Name/Value
Description
Def/FbEq16
100%
63%
100%
Time
Time
Motor thermal time
Motor current
Temperature rise
ACQ80 FW.book Page 126 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...