124 Parameters
Defines the ambient temperature of the motor for the motor
thermal protection model. The unit is selected by parameter
The motor thermal protection model estimates the motor
temperature on the basis of parameters
…
. The
motor temperature increases if it operates in the region above
the load curve, and decreases if it operates in the region
below the load curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust, dirt, etc.
20 °C or
68 °F
-60…100 °C or
-76 … 212 °F
Ambient temperature.
1 = 1°
Defines the motor load curve together with parameters
and
The load curve is
used by the motor thermal protection model to estimate the
motor temperature.
When the parameter is set to 100%, the maximum load is
taken as the value of parameter
(higher loads heat up the motor). The load curve level should
be adjusted if the ambient temperature differs from the
nominal value set in
100%
50…150%
Maximum load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
. Defines the
maximum motor load at zero speed of the load curve. A
higher value can be used if the motor has an external motor
fan to boost the cooling. See the motor manufacturer's
recommendations.
See parameter
.
100%
50…150%
Zero speed load for the motor load curve.
1 = 1%
No.
Name/Value
Description
Def/FbEq16
50
100
150
I/I
N
(%)
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
ACQ80 FW.book Page 124 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...