![ABB ACQ80-04 Series Firmware Manual Download Page 114](http://html.mh-extra.com/html/abb/acq80-04-series/acq80-04-series_firmware-manual_2932114.webp)
114 Parameters
32
Configuration of signal supervision functions 1…6.
Six values can be chosen to be monitored; a warning or fault
is generated whenever predefined limits are exceeded.
See also section
(page
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note:
This word is independent of the drive actions defined
.
0b000
0b0000…0b1111
Signal supervision status word.
1 = 1
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter
) is compared
to its lower and upper limits (
respectively).
The action to be taken when the condition is fulfilled is
selected by
Disabled
Signal supervision 1 not in use.
0
Low
Action is taken whenever the signal falls below its lower limit. 1
High
Action is taken whenever the signal rises above its upper
limit.
2
Abs low
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
Abs high
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
Hysteresis
Action is taken whenever the signal falls below its (hysteresis)
low limit or rises above its (hysteresis) high limit.
7
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note:
This parameter does not affect the status indicated by
.
No action
No warning or fault generated.
0
Warning
Warning
is generated.
1
Fault
Drive trips on fault
2
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Supervision 1 active
is outside its limits.
1
Supervision 2 active
is outside its limits.
2
Supervision 3 active
is outside its limits.
3
Supervision 4 active
is outside its limits.
4
Supervision 5 active
is outside its limits.
5
Supervision 6 active
is outside its limits.
6…15
Reserved
ACQ80 FW.book Page 114 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...