174 Parameters
Defines the stator resistance
R
S
of the motor model.
0.00000 ohm
0.00000…100.0000
0 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
0.00000 ohm
0.00000…100.0000
0 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
0.00 mH
0.00…100000.00
mH
Main inductance. Rev D: 98.11-14 Partoolissa 0.1 = 1 mH.
Range upper limit on the panel ends with.0.02?
1 = 10000
mH
Defines the leakage inductance
σ
L
S
.
0.00 mH
0.00…100000.00
mH
Leakage inductance.
1 = 10000
mH
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00 …100000.00
mH
Direct axis inductance.
1 = 10000
mH
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00 …100000.00
mH
Quadrature axis inductance.
1 = 10000
mH
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the drive is
running.
Asynchronous
motor
Standard squirrel cage AC induction motor (asynchronous
induction motor).
0
Permanent magnet
motor
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet rotor and sinusoidal BackEMF
voltage.
Note:
With permanent magnet motors special attention must
be paid on setting the motor nominal values correctly in
parameter group
. You must use vector control.
If the nominal BackEMF voltage of the motor is not available,
a full ID run should be performed for improving performance.
1
Selects the motor control mode.
Vector
Vector control. Vector control has better accuracy than scalar
control but cannot be used in all situations (see selection
below).
Requires motor identification run (ID run). See parameter
Note:
In vector control the drive performs a standstill ID run at
the first start if ID run has not been previously performed. A
new start command is required after standstill ID run.
Note:
To achieve a better motor control performance, you can
perform a normal ID run without load.
See also section
0
No.
Name/Value
Description
Def/FbEq16
ACQ80 FW.book Page 174 Thursday, February 14, 2019 11:33 AM
Summary of Contents for ACQ80-04 Series
Page 4: ...4 ACQ80 FW book Page 4 Thursday February 14 2019 11 33 AM ...
Page 10: ...10 Table of contents ACQ80 FW book Page 10 Thursday February 14 2019 11 33 AM ...
Page 16: ...16 Introduction to the manual ACQ80 FW book Page 16 Thursday February 14 2019 11 33 AM ...
Page 28: ...28 Using the control panel ACQ80 FW book Page 28 Thursday February 14 2019 11 33 AM ...
Page 54: ...54 Program features ACQ80 FW book Page 54 Thursday February 14 2019 11 33 AM ...
Page 196: ...196 Additional parameter data ACQ80 FW book Page 196 Thursday February 14 2019 11 33 AM ...
Page 220: ...220 Fault tracing ACQ80 FW book Page 220 Thursday February 14 2019 11 33 AM ...