MYLOS
®
Building Automation |
Operation of communication objects 37
MYLOS
®
Building Automation
Operation of communication objects
According to parameter setting, this communication object can be switched by the ON, OFF or Switching input
drive. With Switching the previous value, for example “1”, is directly switched to value “0”. It is important to ensure
that the communication object can be written from the outside. Therefore cyclic sending is interrupted or is not
possible.
18
Relative dimming
Rocker switch 1
3 bit DPT_Control_
Dimming
C,W,T,U
25
Relative dimming
Rocker switch 2
3 bit DPT_Control_
Dimming
C,W,T
A long input operation via this communication object causes an adjusting command “BRIGHTER” or “DARKER”
to be sent over the bus. At the end of the command a Stop command is sent to the input.
34
Disabling LED
Rocker switch 1
1 bit DPT_Enable
C,W
35
Disabling LED
Rocker switch 2
1 bit DPT_Enable
C,W
The “Disabling Led” communication object makes it possible to enable (1) the LED so as that it switches
on or off depending on the operating mode selected from the parameters or to disable it (0) forcing it into a
continuous switching off status.
3.1.4 Shutter rocker switch
No.
Function
Object name
Type of datum
Flags
16
Disabling
Rocker switch 1
1 bit DPT_Enable
C,W
23
Disabling
Rocker switch 2
1 bit DPT_Enable
C,W,T,U
The channel circuitry can be blocked or enabled using the communication object.
A blocked channel behaves as if there was no input signal. Communication objects of the channel are still available.
17
Shutter up-down
Rocker switch 1
1 bit DPT_UpDown
C,T
24
Shutter up-down
Rocker switch 2
1 bit DPT_UpDown
C,W,T,U
This communication object sends a shutter movement control (UP or DOWN) over the bus.
18
Stop/Louvre up-down
Rocker switch 1
1 bit DPT_Step
C,T
25
Stop/Louvre up-down
Rocker switch 2
1 bit DPT_Step
C,W,T,U
Telegram value:
“0” OFF
“1” ON
According to parameter setting, this communication object can be switched by the ON, OFF or Switching input
drive. With Switching the previous value, for example “1”, is directly switched to value “0”. It is important to ensure
that the communication object can be written from the outside. Therefore cyclic sending is interrupted or is not
possible.
34
Disabling LED
Rocker switch 1
1 bit DPT_Enable
C,W
35
Disabling LED
Rocker switch 2
1 bit DPT_Enable
C,W,T