36 Operation of communication objects
| MYLOS
®
Building Automation
MYLOS
®
Building Automation
Operation of communication objects
17
Upper rocker switch
Switching
Rocker switch 1
1 bit DPT_Switch
C,W,T
24
Upper rocker switch
Switching
Rocker switch 2
1 bit DPT_Switch
C,W,T
Telegram value:
“0” OFF
“1” ON
According to parameter setting, this communication object can be switched by the ON, OFF or Switching input
drive. With Switching the previous value, for example “1”, is directly switched to value “0”. It is important to ensure
that the communication object can be written from the outside. Therefore cyclic sending is interrupted or is not
possible.
18
Lower rocker switch
Switching
Rocker switch 1
1 bit DPT_Switch
C,W,T
25
Lower rocker switch
Switching
Rocker switch 2
1 bit DPT_Switch
C,W,T
Telegram value:
“0” OFF
“1” ON
According to parameter setting, this communication object can be switched by the ON, OFF or Switching input
drive. With Switching the previous value, for example “1”, is directly switched to value “0”. It is important to ensure
that the communication object can be written from the outside. Therefore cyclic sending is interrupted or is not
possible.
34
Disabling LED
Rocker switch 1
1 bit DPT_Enable
C,W
35
Disabling LED
Rocker switch 2
1 bit DPT_Enable
C,W
The “Disabling Led” communication object makes it possible to enable (1) the LED so as that it switches
on or off depending on the operating mode selected from the parameters or to disable it (0) forcing it into a
continuous switching off status.
3.1.3 Dimmer rocker switch
No.
Function
Object name
Type of datum
Flags
16
Disabling
Rocker switch 1
1 bit DPT_Enable
C,W,T,U
23
Disabling
Rocker switch 2
1 bit DPT_Enable
C,W
The channel circuitry can be blocked or enabled using the communication object.
A blocked channel behaves as if there was no input signal. Communication objects of the channel are still available.
17
Switching
Rocker switch 1
1 bit DPT_Switch
C,W,T,U
24
Switching
Rocker switch 2
1 bit DPT_Switch
C,W,T
Telegram value:
“0” OFF
“1” ON