32 Operation of communication objects
| MYLOS
®
Building Automation
MYLOS
®
Building Automation
Operation of communication objects
3
Operation of communication objects
No.
Function
Object name
Type of datum
Flags
0
Switching
Output A
1 bit (EIS 1) DPT 1.001
C, W
8
Switching
Output B
1 bit (EIS 1) DPT 1.001
C, W
This object is used to switch an output ON/OFF.
The device receives a switching command via the communication object. If the output is programmed as "normally
open" contact, the relay is closed with a "1" telegram value and opened with a "0" telegram value (and the opposite
is true when it is programmed as "normally open" contact).
1
Block Time function
Output A
1 bit (EIS 1) DPT 1.003
C, W
9
Block Time function
Output B
1 bit (EIS 1) DPT 1.003
C, W
The object is visible if the time function has been enabled in the parameter window “X: Function”. The time function
(delay, stairlights and flashing) can be enabled or disabled using this object. After bus voltage restoration, the object
value can be determined via the "‘Disable time function’ object value after bus voltage restoration" object in the
parameter window “X: Function”. See paragraph 4.2.2 for an application example.
Telegram value“1” disables the time function.
Telegram value“0” enables the time function.
If the time function is blocked only a switching without delay is possible.
Contact position at the moment of inhibition continues and will be changed only with the next switching command.
2
Forced operation
Output A
1 bit (EIS 1) DPT 1.003
C, W
10
Forced operation
Output B
1 bit (EIS 1) DPT 1.003
C, W
This object is visible if in the "Function" parameter window the "Switching status in forced operation" has been
selected as 1 bit object.
If this object contains the value "1", the output is forcedly set at the programmed switching position that has been
configured in the "Function" parameter window. The forced contact position continues until the end. This happens
if a “0” is received via the “Forced operation” object.
2
Forced operation
Output A
2 bit (EIS 8) DPT 2.001
C, W
10
Forced operation
Output B
1 bit (EIS 8) DPT 2.001
C, W