Operation of communication objects 33
MYLOS
®
Building Automation
Operation of communication objects
This object is visible if in the "Function" parameter window the "Switching status in forced operation" has been
selected as 2 bit object.
The output can be controlled forcedly using this object (for example an upper level control). The object value defines
the contact forced position.
- “0” or “1”: The output is not switched forcedly
- “2”: The output is switched forcedly on OFF
- “3” : The output is switched forcedly on ON
3
Scenes
Output A
1 bit non EIS DPT
18.001
C, W
11
Scenes
Output B
1 bit non EIS DPT
18.001
C, W
Using this 8 bit communication object it is possible to send a scene command with a coded telegram.
The telegram contains the corresponding scene number and the indication about whether the scene has to be
recalled or the current switching status must be assigned to it.
The communication object is visible only if the output X in the "Function" parameter window is assigned to at least
a 8 bit scene.
Telegram size (1 byte):
- MXSSSSSS
- (MSB) (LSB)
M:
- 0 – the scene is recalled
- 1 – the scene is stored (if permitted)
X:
- not used
S
- Scene number (1 ... 64: 00000000 ... 00111111)
Value of the 1 byte EIB / KNX telegram
Meaning
decimal
hexadecimal
00 or 64
01 or 65
02 or 66
...
63 or 127
00h or 40h
01h or 41h
02h or 42h
...
3Fh or 7Fh
Recall scene 1
Recall scene 2
Recall scene 3
...
Recall scene 64
128 or 192
129 or 193
130 or 194
...
191 or 255
80h or B0h
81h or B1h
82h or B2h
...
AFh or FFh
Store scene 1
Store scene 2
Store scene 3
...
Store scene 64
4
Switching status
Output A
1 bit (EIS 1) DPT 1.002
C, R, T
12
Switching status
Output B
1 bit (EIS 1) DPT 1.002
C, R, T
This object is always visible.
The object value indicates the relay contact position.
5
Stairlight pre-warning
Output A
1 bit (EIS 1) DPT 1.003
C, T
13
Stairlight pre-warning
Output A
1 bit (EIS 1) DPT 1.003
C, T