MYLOS
®
Building Automation |
Operation of communication objects 39
MYLOS
®
Building Automation
Operation of communication objects
3.1.6 8 bit scene rocker switch
No.
Function
Object name
Type of datum
Flags
16
Disabling
Rocker switch 1
1 bit DPT_Enable
C,W
23
Disabling
Rocker switch 2
1 bit DPT_Enable
C,W
The channel circuitry can be blocked or enabled using the communication object.
A blocked channel behaves as if there was no input signal. The communication
objects of the channel are still available.
17
8 bit scene
Rocker switch 1
1 byte DPT_Unsigned_
Counter_value
C,W,T,U
24
8 bit scene
Rocker switch 2
1 byte DPT_Unsigned_
Counter_value
C,W,T,U
This communication object sends the following values over the bus to fulfil the scene setting.
1-Byte value [ON/OFF]
EIS 1
DPT 1.001 switching command
22
Store scene
Rocker switch 1
1 bit DPT_Enable
C,W,T,U
29
Store scene
Rocker switch 2
1 bit DPT_Enable
C,W,T,U
This communication object appears only with the option “object value = 1”.
This option can be set in the parameter "Store scene". This communication object is used to start scene storage
over the bus.
The function depends on the type of scene storage.
34
Disabling LED
Rocker switch 1
1 bit DPT_Enable
C,W
35
Disabling LED
Rocker switch 2
1 bit DPT_Enable
C,W
The “Disabling Led” communication object makes it possible to enable (1) the LED so as that it switches
on or off depending on the operating mode selected from the parameters or to disable it (0) forcing it into a
continuous switching off status.