18
www.hotwater.com
316888-001 Rev. 00 dRaFt Jun 28 245
The appliance and its gas connections must be leak tested
before placing the appliance in operation. Use a leak test
solution, not a match or open
fl
ame.
NOTE:
An alternate location for the gas line entry is
possible. Drill a suitable hole centered on the crosshairs
on the left side panel.
Use pipe joint compound or Te
fl
on tape marked as being
resistant to the action of petroleum [Propane (L.P.)]
gases.
The appliance and its gas connection must be leak tested
before placing the appliance in operation.
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of 1/2 psi (3.5 kPa).
It shall be isolated from the gas supply piping system
by closing its individual manual shut-off valve during
the pressure testing, the gas supply piping system at
test pressures equal to or less than 1/2 psi (3.5 kPa) is
considered isolated.
SEDIMENT TRAPS
A sediment trap shall be installed as close to the gas inlet
of the water heater as practical at the time of water heater
installation. The sediment trap shall be either a tee
fi
tting
with a capped nipple in the bottom outlet or other device
recognized as an effective sediment trap.
Contaminants in the gas lines may cause improper
operation of the gas control valve that may result in
fi
re
or explosion. Before attaching the gas line be sure that all
gas pipe is clean on the inside. The sediment trap must
be readily accessible. Install in accordance with the “Gas
Piping” section. Refer to the current edition of CAN/CSA-
B149.1, the Natural Gas and Propane Installation Code.
GAS LINE PURGING
Air may be present in the gas lines and could prevent
the burner from lighting on initial start-up. The gas lines
should be purged of air by a quali
fi
ed service technician
after installation of the gas piping system.
HIGH ALTITUDE INSTALLATIONS
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
• Special consideration must be taken
with installations above 3.352m (11,000').
• Please contact an AO Smith qualified
service agent to obtain proper setup and
instructions before lighting.
• Failure to implement the proper setup
will result in improper and inefficient
operation of the appliance resulting in
production of increased levels of carbon
monoxide gas in excess of the safe
limits which could result in serious
personal injury or death.
Breathing Hazard - Carbon Monoxide Gas
WARNING
The heater is set at the factory to operate at altitudes from
sea level to 1,067m (3,500 ft.). Accessory kits are available
to allow the heater to operate at altitudes higher than
1,067m (3,500 ft.). These accessory kits are listed in the
table below. Instructions for installing these accessories
are included in the kits.
Altitude m (ft.)
Kit #
1,067 -1,981 (3,501 - 6,500)
9007439005
1,981 - 2,591 (6,501 - 8,500)
9007440005
2,591 - 3,352 (8,501 - 11,000)
9007441005
Rated inputs are suitable up to 3,352m (11,000 ft.)
elevation. Consult the factory for installation at altitudes
over 3,352m (11,000 ft.).
WARNING: THIS HIGH EFFICIENCY WATER HEATER
IS CERTIFIED FOR USE AT AN ALTITUDE OF 11,000
Ft. (3,352 METERS). HOWEVER, FOR USE AT
ALTITUDES OVER 3,500 Ft. (1,067m) THE PCB MUST
BE CHANGED.
Some gas utility companies derate their gas for altitude,
making it unnecessary to modify the water heater for high
altitude installations. Call the local gas or utility company
to verify BTU content.
Summary of Contents for HYB-90N
Page 4: ...4 www hotwater com 316888 001 Rev 00 dRaFt Jun 28 245 GENERAL SAFETY...
Page 25: ...316888 001 Rev 00 dRaFt Jun 28 245 www hotwater com 25 FIGURE 31...
Page 52: ...599 Hill Street West Fergus ON Canada N1M 2X1 PHONE 1 888 479 8324 www hotwater com...
Page 109: ...www hotwater com 57 NOTES...
Page 110: ...58 www hotwater com NOTES...
Page 111: ...www hotwater com 59 NOTES...
Page 112: ...599 rue Hill Ouest Fergus ON Canada N1M 2X1 PHONE 1 888 479 8324 www hotwater com...