Chapter 6 Installation of External Power Cables and Grounding Cables
Area A
Area B
Way Number
Input Terminal
Output Terminal
Output Terminal
Input Terminal
–48 V (
Ⅱ
)
–48 V A 3–4
–48 V B 3–4
–48 V (
Ⅱ
)
Way 2
–48 VRTN (
Ⅱ
)
–48 VRTN(A) 3–4
–48 VRTN(B) 3–4
–48 VRTN (
Ⅱ
)
–48 V (
Ⅲ
)
–48 V A 5–10
–48 V B 5–10
–48 V (
Ⅲ
)
Way 3
–48 VRTN (
Ⅲ
)
–48 VRTN(A)
5–10
–48 VRTN(B) 5–10
–48 VRTN (
Ⅲ
)
-
The maximum
input current on
each way is 100 A.
Output terminal 1–4: The maximum
output current on one way is 60 A.
Output terminal 5–10: The maximum
output current on one way is 60 A
(Breakers of other rated currents can
also be configured as needed).
The maximum input
current on each
way is 100 A.
6.2 Cabling Requirements
Routing Principles
l
Power cables and grounding cables should be routed in a smooth and straight manner,
see
.
Figure 6-3 Routing of Power Cables and Grounding Cables
1.
Power Cable
2.
Grounding Cable
l
If a cable is not long enough, use a longer cable. Do not connect or solder two or
more short cables to make a long one.
6-3
SJ-20141121113158-006|2014-12-20 (R1.0)