Chapter 5 Cabinet Installation
23. Verify that the horizontal and vertical deviations of cabinets in a row are in an accept-
able range.
The deviation should be less than 3 mm. If it does not meet the requirement, adjust
cabinets.
24. (Optional) Install a shockproof assembly on the cabinet if necessary.