GEN III
-VVT
VOTE BASED AUTO CHANGEOVER VAV
WITH WIRELESS THERMOSTATS
DEVICE
ID
DESCRIPTION
CONTROL BOARD
C1
GEN III CONTROLLER
CONTROLS 2-20 ZONE DAMPERS ONLY 1 24VAC 40VA TRANSFORMER
POWERS ALL SUPPLY DAMPERS
THERMOSTAT
T1 -T20
ZONEX WIRELESS THERMOSTAT
REMOTE SENSOR
RS
ZONEX WIRELESS REMOTE SENSOR
SYSTEM TRANSFORMER
TR1
24VAC/40VA TRANSFORMER SIZED @ (2VA PER ZONE DAMPER)
DAISY CHAIN DAMPER TO DAMPER
BYPASS TRANSFORMER
TR2
IND. 24VAC/40VA TRANSFORMER TO POWER THE BYPASS DAMPER
SUPPLY / RETURN AIR
LAT DISCHARGE SENSORS
LAT
SUPPLY LAT LOCATED BEFORE THE BYPASS. RETURN LAT
LOCATED AFTER THE BYPASS
ZONE DAMPER MOTOR
DM
SUPPLIED WITH ZONE DAMPER (FACTORY PRE-WIRED)
INTEGRATED
STATIC PRESSURE CONTROL
IPC
SUPPLIED WITH THE ZONEX BYPASS DAMPER (FACTORY PRE-WIRED)
SPT
STATIC PRESSURE TUBE
LOCATED AFTER THE BYPASS BEFORE THE FIRST SUPPLY TAKEOFF
BYPASS DAMPER MOTOR
BP-DM
SUPPLIED WITH ZONEX BYPASS DAMPER (FACTORY PRE-WIRED)
VISIT OUR ON-LINE CATALOG AT ZONEXPRODUCTS.COM
FOR APPLICATIONS ASSISTANCE CALL 800-228-2966
RS485 COMMUNICATION LINK
WIRELESS COMMUNICATION
COMMUNICATES WITH WIRELESS DAMPER BOARD AND THERMOSTAT
TWISTED PAIR WIRING -BELDEN 8740 DAISY CHAIN DAMPER TO DAMPER
GEN III-VVT
POWER SWITCH
ID / SYNC
24VAC IN
24VAC OUT
TO UNIT TERMINALS
RS485 COMMUNICATION LINK ( BELDEN 8740)
STATUS LIGHTS
AUX SENSOR (AS)
LEAVING AIR SENSOR (LVAIR)
OUTSIDE AIR SENSOR (OA)
RETURN AIR SENSOR (RA)
DAISY CHAIN 24VAC AND
DATALINK CABLE (BELDEN 8740)
TO ALL ZONE DAMPER BOARDS -
EXPANDABLE TO 20 ZONES
C1
MODULATING DAMPER
DM-1
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
MODULATING DAMPER
DM-4
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
MODULATING DAMPER
DM-3
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
MODULATING DAMPER
DM-2
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
MC
RC
RO
MC
RC
RO
MC
RC
RO
MC
RC
RO
6