GEN III
– VVT
SELECT
EXIT
SYSTEM CONFIGURATION
13) SYSTEM BALANCE
14) TEMP FORMAT
15) CLOCK
16) PASSWORD
SET CLOCK
BACK
EXIT
NEXT
02
: 36 PM WED
SET CLOCK
BACK
EXIT
NEXT
02 :
36
PM WED
SET CLOCK
BACK
EXIT
NEXT
02 : 36
PM
WED
SET CLOCK
BACK
EXIT
NEXT
02 : 36 PM
WED
SELECT
EXIT
SYSTEM CONFIGURATION
5) HIGH / LOW LIMIT CTR
L
6) SECOND STAGE DELAY
7) OVERRIDE HOURS
8) PRIORITY VOTE
SET LOW CUT-OUT
HIGH
EXIT
LOW
45
SET HIGH CUT-OUT
HIGH
EXIT
LOW
145
Set Clock
From the MONITOR STAT the master clock is set for all system devices. To set the clock time and day,
access SYSTEM CONFIGURATION Menu on the MONITOR STAT, use the UP or DOWN buttons to highlight
MENU Item 15 — CLOCK and press select. Hour option will be highlighted, use the UP or DOWN button to
change the hour to current hour, once current hour is displayed, press NEXT button to highlight
MINUTES option and use the UP or DOWN button to select current minutes. Once minutes are set press
NEXT button and select AM or PM by using the UP or DOWN buttons, then press NEXT to select the
day of the week using the UP or DOWN buttons to select current day. Once hour, minutes, AM/PM,
and day of week are set press the exit button to save and return to System Configuration Menu.
Confirm High/Low Limits
Factory defaults for GAS/ELECTRIC units are set for 45 degrees Low Limit and 145 degrees High Limit.
Heat Pump O and B machines are set for 45 degrees Low Limit and 115 degrees High Limit. These may be
adjusted in the field to meet unit specification. To confirm or adjust, access the SYSTEM CONFIGURATION
menu on MONITOR STAT, use the UP or DOWN buttons to highlight Menu Item 5 HIGH/LOW LIMIT and press
select. Press HIGH button to show High Limit temperature, press LOW button to show Low Limit temperature.
If adjustment is needed, use the UP or DOWN button to reset temperature. When complete, press exit button
and YES to save settings and return to System Configuration Menu.
17