SELECT
EXIT
ZONE SETUP
A. SYNCHRONIZE DAMPER
B. CALIBRATE
C. SET AUXILIARY HEAT
D. ENERGY SAVING MODE
SYNC DAMPER?
ID: 01
NO
YES
Sync Monitor Thermostat with GEN III Controller
Identify which of the thermostats will be the Monitor Stat and turn ON GEN III Controller (GEN III controller
will flash blue communications light when energized). The monitor will now be the primary user interface to
make and execute control decisions for the system.
On Monitor STAT press the MENU button then SET button and hold both to enter SYSTEM CONFIGURATION
MENU. Use UP or DOWN button to highlight item 11 – SYNC MONITOR and press select, when asked SYNC
MONITOR? Go to the GEN III controller and press the ID button until the BLUE LED flashes continuously.
Press YES on MONITOR STAT, it will take up to 2 minutes for MONITOR to SYNC with GEN III controller. When
MONITOR is synced with GEN III, display will report SYNC SUCCESSFUL.
Note: Only one thermostat in the system can be the MONITOR STAT.
The blue light flashing indicates communication between the GEN III controller and the communicating damper board.
While still in ZONE SETUP use the UP or DOWN to highlight and select item (A) SYNCHRONIZE DAMPER. Go
to the damper control board and press the SYNC button and hold until blue communications light flashes
continuously and then press YES on thermostat to Synchronize. When damper and stat are synced, the
message SYNC IS COMPLETE will be displayed on the thermostat. Press Exit to return to normal operation.
Continue to the next damper and thermostat in daisy chain and repeat increasing stat IDs in numerical order.
Communicating
Damper Board
SELECT
EXIT
SYSTEM CONFIGURATION
9) FAN MODE
10) UNIT TYPE
11) SYNC MONITOR
12) MAVERICK
SYNC MONITOR?
NO
YES
GEN III-VVT
POWER SWITCH
ID / SYNC
24VAC IN
24VAC OUT
TO UNIT TERMINALS
RS485 COMMUNICATION LINK ( BELDEN 8740)
AUX SENSOR (AS)
LEAVING AIR SENSOR (LVAIR)
OUTSIDE AIR SENSOR (OA)
RETURN AIR SENSOR (RA)
GEN III-VVT
ID / SYNC
24VAC IN
24VAC OUT
Note: Before syncing Monitor Thermostat, ensure all thermostats are first synced to their respective damper.
C
C
R
R
RX
RX
TX
TX
MC
RO
RC
C
AUX
TS
TS
SYNC
BUTTON
STATUS LIGHTS
GEN III
– VVT
15