BASEBOARD
TO ACCESS THE
ZONE SETUP MENU
Press any key to display operations mode on the thermostat then press
Menu
once
Then press and hold the
Menu
and
Auto
button simultaneously until the Zone Setup Menu is displayed.
Then use the
up
and
down
buttons to scroll through Zone Setup Menu options.
Two menus are available at each zone thermostat. A Zone Setup Menu and System Configuration Menu.
ZONE
SETUP MENU
is available from every thermostat in the system.
SYSTEM CONFIGURATION MENU
may be
viewed on every thermostat BUT only controllable from the assigned MONITOR THERMOSTAT in the system.
A. Synchronize the stat to its respective damper
B. Calibrate the zone thermostat
C. Set Auxiliary heat
B
CALIBRATE
THERMOSTAT
If you require field calibration return to the Zone Setup Menu and scroll to
item (B)
CALIBRATION
.
Use the
up
and
down
buttons to calibrate the temperature display with your
external thermostat, then push
EXIT
to save changes.
Confirm temperature display now reports the updated room temperature you
provided.
CALIBRATE THERMOSTAT
EXIT
A
SYNCHRONIZE
DAMPER
1. Place damper in Sync mode by pushing the black button in the lower corner of
the communicating damper board.
This will energize a blue flashing light indicating Sync or pairing mode is active.
2. Once damper light is blinking and in active Sync mode return to the thermostat
and enter Zone Setup Menu. Use the
up
and
down
buttons to scroll and
highlight item (A)
SYNC DAMPER
. Press
Select
confirm ID matches
the ID# you assigned earlier. Push
Yes
to Sync.
SYCHRONIZE DAMPER
YES
NO
PUSH UP DOWN TO CALIBRATE
F
O
Once your zone thermostat has been assigned an ID number you will need to
synchronize with its corresponding zone damper. Two steps are required to Sync the
thermostat to the damper.
Thermostat is equipped with an accurate temperature sensor.
SYNC DAMPER?
ID: 01
74.1
c
SET
AUXILIARY HEAT
Access the Zone Setup Menu select item (C)
SET AUXILIARY HEAT
press
Select
.
Select BASEBOARD, BASEBOARD W1 or REHEAT using the
up
and
down
arrows or
button
Then press
Select
and enter the temperature range you would like to energize
base board or reheat.
Default settings initiate supplemental heat 2 degrees below the heat set point. You
can select 2,3,or 4 degrees using the
up
and
down
buttons.
SET AUXILIARY HEAT
EXIT
BASEBOARD W1
REHEAT
SELECT
AUX HEAT BAND
EXIT
2 F
O
AUX HEAT BAND
D. Place Stat in Energy Savings mode
E. Set System ID
F. Set Stat ID
G. Set 7-Day Schedule
The ZONE SETUP MENU allows you to:
GEN III
– VVT
24