SELECT
EXIT
ZONE SETUP
E. SET SYSTEM ID
F. SET STAT ID
SELECT
EXIT
ZONE SETUP
E. SET SYSTEM ID
F. SET STAT ID
SAVE
EXIT
INACTIVE
STAT ID:
001
SAVE
EXIT
SYS ID:
001
COMMISSIONING START-UP
Use the UP or DOWN button to highlight item (E) SET SYSTEM ID and press SELECT. Set the SYSTEM ID to 001
for the first GEN III controller in the building. (If you have more then one GEN III controller in the building you
will need to give each one its own SYSTEM ID ranging from 001-100). Once System ID is set, press EXIT to
SAVE.
While still in the Zone Setup screen, use the UP or DOWN buttons to highlight item (F) SET STAT ID menu item
and then press SELECT. Set STAT ID for the first stat to 001, place provided label #1 on the inside of the
thermostat sub-base (All stats are SYNCED with its damper ID 001 to 020, maximum of 20 zone on one GEN III
system). Once System ID is set, press EXIT to SAVE.
Sync Dampers and Wireless Thermostats
Each Damper will need to be ID’d and Synced with its control thermostat. Beginning with the first damper in
the daisy chain closest to the GEN III controller, place provided label #1 on the damper. Locate associated
zone thermostat and insert batteries, confirm display appears on stat. If no display is seen, check battery
installation. At this time power and turn on the GEN III controller at the ON/OFF switch located on the left
hand corner of the GEN III controller.
On the wireless thermostat, press the MENU button followed by the OFF/AUTO button, release when display
reads ZONE SETUP.
UP
DOWN
Note: You can only Sync one damper at a time.
COMMISSIONING
AND START UP
GEN III
– VVT
14