WIRELESS REMOTE SENSOR
GEN III
– VVT
Description
The wireless remote sensor part # WRS is a microprocessor based, auto
changeover, programmable communicating zone thermostat without a
local display. The zone sensor controls modulating round, rectangular
dampers or WD-Fusers. The communicating remote sensor is used with the
GEN III-VVT zoning system.
The wireless remote sensor controls and modulates zone dampers based on
variance from set point to a position that will match the supply load to the
demand requirement. When the HVAC unit is running, if a remote sensor is
not calling or is calling for the opposite mode, its corresponding damper
fully closes. When the HVAC unit is not running, the remote sensor will
instruct its corresponding damper to go into Vent mode to provide
ventilation, if the indoor blower fan is running continuously.
The Remote Sensor provides local adjustment of +/- 2 degrees from set
point using the sensors slide pot. Auxiliary or supplemental heat sources,
i.e. base board, radiant panels, or reheat coils may also be controlled and
energized from each remote sensor if required.
Use a Monitor thermostat to set and review one or more remote sensors.
Sensor can be setup with daily schedules, priority votes and override
functions which are all programmed to the remote sensor from the Monitor
thermostat.
A Wireless Occupancy Remote Sensor is also available, and when it detects
a first body movement it will quickly blink the LED and read the slide pot.
Battery Installation
1.
Remove wireless remote sensor cover plate.
2.
Install two AAA batteries provided with the wireless remote sensor.
Wireless Remote Sensor
Wireless Occupancy Remote Sensor
Procedure To Synchronize ID On Wireless Remote Sensor:
Use any a wireless LCD stat to sync up.
Hold down the button on the damper control board that is needed to pair
with the wireless remote sensor until the LED blinks.
Hold down the button on the wireless remote sensor until its LED blinks.
Go to Zone Setup by holding down Menu and Auto and select (E)
System ID and set it to what your system ID is.
While still in the Zone Setup, select (F) Stat ID and set your ID.
Continue to menu item (A) in Zone Setup to synchronize damper.
When the screen displays “Synch is completed” and both LEDs’ stop
blinking, synchronization is successful.
Remember to change the ID on the wireless LCD stat to a different ID to
avoid ID conflicts, because now the wireless remote sensor and the
wireless LCD stat have the same ID.
1.
2.
3.
4.
5.
6.
7.
8.
To clear the wireless ID, Remove the batteries and hold down the button while putting the batteries back in for 5 seconds.
This will reset the wireless remote sensor system ID to 0 and stat ID to 21 to avoid communication.
AAA
AAA
BB
BB W1
REHEAT
AAA
AAA
BB
BB W1
REHEAT
SELECT
EXIT
ZONE SETUP
E. SET SYSTEM ID
F. SET STAT ID
AAA
AAA
BB
BB W1
REHEAT
AAA
AAA
BB
BB W1
REHEAT
AAA
AAA
BB
BB W1
REHEAT
AAA
AAA
BB
BB W1
REHEAT
AAA
AAA
BB
BB W1
REHEAT
35