04
SYSTEM
DIAGNOSTIC
ACTIVE CHANNELS
DIAGNOSTIC INFO
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(4) SYSTEM DIAGNOSTIC menu item, (instructions above).
To review active communicating channels, leaving air temperature, return and
outside air may also be reviewed by pressing the NEXT button.
Press
Exit
to return to the System Configuration screen.
Note: If RF Error or RS 485 Error displays on stat, review the following.
A. Confirm the communicating damper board light is flashing.
B. Confirm STAT ID and re-sync with communicating damper board.
C. Move stat closer to the communicating damper board to enhance
communication.
05
HIGH/LOW
LIMIT
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
(5) HIGH/LOW LIMIT CTRL menu item, (instructions above).
Press HIGH button to access and set High Cut-out.
Use the
up
or
Down
to set the desired HIGH CUT-OUT TEMPERATURE LIMIT.
Press
LOW
button to advance to the Low Cut-Out Temperature Limit.
Use the
up
or
Down
to set the desired LOW CUT-OUT TEMPERATURE LIMIT.
Press
EXIT
to advance to Save the settings.
Press
yes
to save the settings
.
SELECT
EXIT
SYSTEM CONFIGURATION
5) HIGH/LOW LIMIT CTRL
6) SECOND STATE DELAY
7) OVERRIDE HOURS
8) PRIORITY VOTE
HIGH
LOW
EXIT
SET HIGH CUT-OUT
140
SET HIGH/LOW CUT-OUT
HIGH/LOW LIMIT CONTROL
SAVE DATA
EXIT
ACTIVE CHANNELS:
1 2 3 4 5 6 7 8 9 10 11
BACK
NEXT
BACK
NEXT
This function allows the user to review the current conditions
for the GEN III System. Number of Channels in the system – How many zones are
communicating, Leaving Air Temperature, Return Air Temperature, Outside Air
Temperature all from the Monitor Stat.
For system protection the GEN III has high and low limit protections built into the
MONITOR STAT configurations. Factory defaults for Gas/Electric operations are High
Limit of 145 F and Low Limit of 45 F, for Heat Pump operations factory defaults are High
Limit of 115 F and Low Limit of 45 F. These can be field configured as required.
SYSTEM DIAGNOSTIC
SCREEN
EXIT
LEAVING AIR:
RETURNED AIR:
OUTSIDE AIR:
59
72
81
NEXT SCREEN
Use the
up
or
Down
to set the desired OCCUPIED COOL temperature.
Press
NEXT
to advance to the Occupied Heat menu.
NEXT SCREEN
Use the
up
or
Down
to set the desired OCCUPIED HEAT temperature.
Press
NEXT
to advance to the Unoccupied Cool menu.
NEXT SCREEN
Use the
up
or
Down
to set the desired UNOCCUPIED COOL temperature.
Press
NEXT
to advance to the Unoccupied Heat menu.
NEXT SCREEN
Use the
up
or
Down
to set the desired UNOCCUPIED HEAT temperature.
Press
Exit
when you have set the scheduled on/off times for each thermostat.
Press
yes
to save the settings.
Note: Display goes blank during the Unoccupied Mode to conserve battery life.
Touching any button will immediately refresh the display.
BACK
NEXT
EXIT
SET OCCUPIED COOL
69
OCCUPIED COOL
SET OCCUPIED COOL
THEN OCCUPIED HEAT
BACK
NEXT
EXIT
SET UNOCCUPIED COOL
90
UNOCCUPIED COOL
SET UNOCCUPIED COOL
THEN UNOCCUPIED HEAT
29