SELECT
EXIT
SYSTEM CONFIGURATION
9) FAN MODE
10) UNIT TYPE
11) SYNC MONITOR
12) MAVERICK
FAN MODE
EXIT
AUTO
FAN MODE
EXIT
ON
SELECT
EXIT
SYSTEM CONFIGURATION
1) SCHEDULE
2) LOCK
3) MASTER TEMP SET
4) SYSTEM DIAGNOSTIC
TEMPSET ID
BACK
EXIT
NEXT
STAT ID : GLOBAL
NO
YES
SELECT GLOBAL ID?
SET OCCUPIED COOL
BACK
EXIT
NEXT
OCCUPIED COOL 70
NO
YES
SAVE DATA?
GEN III
– VVT
Set Fan Operation
Configuration of FAN is set at the factory for AUTO operation, when there is a call for HEAT or COOL, fan will
run. If continuous fan is required, fan will need to be configured for fan ON and will run anytime during
Occupied time, and AUTO during unoccupied. To set fan mode,
SYSTEM CONFIGURATION
Menu on the
MONITOR STAT, use the UP or DOWN buttons to highlight MENU Item 9 FAN MODE. AUTO or ON will
appear on the display, use the UP or DOWN button to change FAN MODE, when desired mode is displayed
press exit to return to
SYSTEM CONFIGURATlON
Menu.
Confirm Cool Call and Damper Operation
From the MONITOR STAT access
SYSTEM CONFIGURATION
Menu and highlight MASTER TEMP SET menu
option and press select. TEMP SET ID will appear on display, using the UP and DOWN buttons, select
STAT ID:
GLOBAL
and press NEXT button. When prompted with
SELECT GLOBAL ID
press YES. SET OCCUPIED COOL
- using the UP or DOWN buttons select a temperature lower than building temperature and press EXIT to save
and set all thermostats in cooling mode. Within 2 minutes, a call for cooling will be made from GEN III
controller. Confirm Y1 and G lights are on at the GEN III controller. Go to each zone and confirm damper is
open and “ON” appears on thermostat display indicating an active COOL CALL has been received. Once all
dampers are confirmed open, satisfy cooling calls at each wireless stat. At each zone stat, raise COOL set point
by pressing SET button and using the UP button to raise the set point. Confirm “ON” disappears and damper
closes once call is satisfied. Continue to satisfy all cool calls one at a time until all calls are satisfied and
dampers are closed. If damper does not close confirm wiring installation.
CONFIRM
SYSTEM OPERATION
18