TO ENTER
System Configuration
Press and hold the
Menu
followed by the
SET
button simultaneously until system configuration is displayed.
Then use the up and down button to scroll through the system configuration options.
Press the
up
or
Down
button to change to YES.
Press
Exit
to reset MONITOR STAT to default settings
Press
Exit
to return to normal operations display
ON : 6:00 A.M. – Set back 6:00 P.M.
M-F operating schedule
Saturday and Sunday will follow Unoccupied schedule.
20
MFG
DEFAULTS
1
SCHEDULE
UNLOCKED
2
LOCK
Occupied Cool 75 Unoccupied Cool 90
Occupied Heat 70 Unoccupied Heat 60
3
MASTER TEMPERATURE SET
No factory default required
4
SYSTEM DIAGNOSTIC
LOW limit
45
degrees
High limit Gas or Electric
145
degrees
5
HIGH LOW LIMIT
5 Minutes
6
SECOND STAGE DELAY
2 hours
7
OVERRIDE HOURS
1
8
PRIORITY
AUTO
9
FAN MODE
Gas / Electric
10
UNIT TYPE
No action required
11
SYNC MASTER
Disable
12
MAVERICK
No action required
13
SYSTEM AIR BALANCE
Fahrenheit
14
TEMP FORMAT
No action required
15
CLOCK
000
16
PASSWORD
20
17
NUMBER OF DAMPERS
No action required
18
LAT CALIBRATION
Disable
19
MORNING WARM UP
System ID
– 001
Energy Savings Mode
20
FACTORY DEFAULTS
EXIT
SET DEFAULT
NO
While in SYSTEM CONFIGURATION menu, press
Down
and press
SELECT
on the
MFG DEFAULTS menu item, (instructions above).
SET DEFAULT
If there is a need to return the MONITOR stat and GEN III controller to factory defaults,
MFG DEFAULT can be used to reset controls to the manufacturer’s defaults. Once this
has been done, technician will need to review configuration settings and set as needed
for proper system operations.
If assistance is needed, call Tech Support at (800) 228-2966
Manufacturers System Defaults
34