35
Default Thermostat Set Point Programming
Global default set points can be established from the
GEN II
controller.
The following procedure will provide a 75°F (23°C) Cool and 70°F (21°C) Heat occupied set point
along with Unoccupied 58°F (14°C) Heat and 85°F (29°C) Cool set point for every thermostat in the
system. This handy feature minimizes visits to the thermostats. To establish these default set
points:
1.
EH
jumper (F) - place the jumper over both pins.
2. Press the
SET
and
DN
button (H) simultaneously to engage default set points.
3. Remove the EH jumper, and place on one pin to put controller back into normal operation.
4. To view the unoccupied set points place the Night / Day switch (L) to the NIGHT position.
Following a poll, the thermostat backlights will turn off; and the unoccupied set points will be
displayed.