15
While in the Thermostat Advanced Menu,
Select
Aux Heat
Select the the desired auxiliary heat operation and dead band
Tap to save changes, to return to the home screen tap
Note
:
Reheat has a fixed 2° dead band.
While in the Thermostat Advanced Menu,
Select
SET ID
Use the and arrows to set the new ID ranging from 1-17
Tap to save changes, to return to the home screen tap
THERMOSTAT ADVANCED MENU
To access the Thermostat Advanced Menu: Tap on the degree symbol next to the room temp .
The degree symbol will change color from white to green and then tap .
The
THERMOSTAT ADVANCED MENU
allows you to:
Set ID Select damper type Select Menu Type
Select Aux Heat Temp Source Diagnostic
STAT ID
Every thermostat in the system needs a unique ID. They must be ID’ed in
numerical order the way the communication wire is daisy chained. No duplicate
addresses.
The zone thermostat provides the following Auxiliary Heat options; Baseboard,
Baseboard W1 and Reheat with configurable dead band of 2°, 3°, or 4°.
SELECT AUX HEAT
EzTouch ADVANCED MENU
01
03
id
1
select aux heat
baseboard-db2
select damper type
round
select temp source
duct
select menu type
advanced