❹ Troubleshooting

•  If a problem occurs, before you contact your retailer, please carry out these few simple checks 

using the following tables. 

•  If the problem continues, contact your retailer.

• 

: Actions to be performed by a qualified technician only

  

4.1 I  Appliance behaviour

The appliance 

does not start 

heating straight 

away

• 

When the setpoint temperature is reached, the heat pump stops heating: the water temperature 

is higher than or equal to the setpoint temperature.

• 

When the water flow rate is zero or is not enough, the heat pump stops: check that the water 

is circulating correctly in the heat pump (see § "2.2 I  User interface presentation") and that the 

hydraulic connections are correct.

• 

The heat pump stops when the outdoor temperature falls below -8 °C.

• 

It may be that the heat pump has detected an operating fault (see § "4.2 I  Error code display"). 

• 

If you have checked these points and the problem persists: contact your retailer.

The appliance 

is discharging 

water 

• 

Often called condensates, this water is the moisture contained in the air which condenses on 

contact  with  certain  cold  mechanisms  in  the  heat  pump,  especially  on  the  evaporator.  The 

damper the air, the more condensates your heat pump will produce (your appliance may drain 

several litres of water per day). This water is recovered at the base of the heat pump and drained 

by the condensate drainage elbow (see § "1.2 I  Hydraulic connections"). 

• 

To check that the water is not coming from a leak in the pool circuit on the heat pump, shut 

down the heat pump and run the filter pump to circulate water in the heat pump. If the water 

continues to flow through the condensate drainage lines, there is a water leak in the heat pump: 

contact your retailer.

The evaporator is 

iced over

• 

Your heat pump will soon switch to its defrost cycle to melt the ice.

• 

If your heat pump cannot manage to defrost its evaporator, it will stop itself; this means that the 

outdoor temperature is too low (below -8 °C).

The appliance is 

"smoking"

• 

The machine has come to the end of the defrost cycle; water has changed to gaseous state and 

passes through the grid.

• 

If your heat pump is not in its defrost cycle, this is not normal. Switch off and disconnect the 

heat pump immediately and contact your retailer.

The appliance is 

not working

• 

 If there is no display, check the power voltage and the fuses.

• 

When the setpoint temperature is reached, the heat pump stops heating: the water temperature 

is higher than or equal to the setpoint temperature.

• 

When the water flow rate is zero or is not enough, the heat pump stops: check that the water is 

circulating correctly in the heat pump (see § "2.2 I  User interface presentation").

• 

The heat pump stops when the outdoor temperature falls below 

 

-8°C or rises above +35°C.

• 

It may be that the heat pump has detected an operating fault (see § "4.2 I  Error code display"). 

The appliance 

is working 

but the water 

temperature 

does not increase

• 

Check that the automatic water filling controller (see diagram in § "2.3 I Operation") is not 

stuck in the open position: this will keep supplying cold water into the pool and will prevent the 

temperature from rising.

• 

There is too much heat loss: install a heat insulated cover on your pool.

• 

The heat pump is unable to capture enough calories as its evaporator is clogged with dirt: clean 

it to restore its efficiency (see § "3.2 I  Maintenance").

• 

Check that the external environment is not hindering the heat pump (see § "❶ Installation").

• 

 Check that the heat pump is the right size for this pool and its environment.

The fan is 

running but 

the compressor 

stops from time 

to time with no 

error message

• 

If  the  outdoor  temperature  is  low,  the  heat  pump  performs  defrost  cycles  under  normal 

operation.

• 

The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 

it to restore its performances (see § "3.2 I  Maintenance").

The appliance 

trips the circuit 

breaker

• 

 Check that the circuit breaker is correctly dimensioned and that the cable section used is 

appropriate (see § "5.2 I Technical specifications").

• 

 The supply voltage is too low: contact your electricity supplier.

Содержание PM40 Series

Страница 1: ...H0686400_REVA 2020 02 More documents on www zodiac com PM40 Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Страница 2: ......

Страница 3: ...nsible for their safety Children must be supervised to ensure that they do not play with the appliance This appliance must not be used by children under 8 or by adults whose reduced physical sensoryor...

Страница 4: ...t separation in all poles allowing for complete disconnection in the event of category III overvoltage the instructions shall specify that disconnection means must be integrated into the fixed wiring...

Страница 5: ...EU 517 2014 In order to comply with the applicable standards and regulations in terms of the environment and installation in particular French decree No 2015 1790 and or European regulation EU 517 201...

Страница 6: ...where the appliance is equipped with the optional pressure gauge The high pressure circuit pipes are made of copper and have a diameter equal to or greater than 1 5 8 A certificate as indicated in 2...

Страница 7: ...orming any maintenance task check that the area is open and well ventilated Suitable ventilation must be provided throughout the maintenance task to allow any refrigerant that could be released into t...

Страница 8: ...of the cable glands etc Make sure that the appliance is properly fixed Make sure that the seals or insulating materials are not deteriorated to the point that they no longer prevent a flammable atmos...

Страница 9: ...to take account of the product s flammability The following procedure must be followed remove the refrigerant purge the circuit with an inert gas optional for A2L drain optional for A2L purge with an...

Страница 10: ...ocated on the scales before starting recovery operations 7 Start the recovery unit and operate as per its instructions 8 Do not overfill the cylinders no more than 80 of the volume must be filled with...

Страница 11: ...have any doubts contact the manufacturer The recovered refrigerant must be sent to the refrigerant supplier in its recovery cylinder with a waste transfer note Do not mix different refrigerants in th...

Страница 12: ...to contact your retailer Write down your retailer s contact details to help you find them more easily and fill in the product information on the back of the manual your retailer will ask you for this...

Страница 13: ...llation on a roof a balcony or any other support Front Rear Anti vibration pads View of the appliance base from below for installing the anti vibration blocks The appliance must not be installed With...

Страница 14: ...o work on the appliance Water inlet valve By pass valve Water outlet valve Water inlet adjustment valve optional Water outlet adjustment valve optional Water treatment system To evacuate the condensat...

Страница 15: ...in the country where it is installed The appliance is provided for connection to a general power supply with a TT or TN S neutral regime Electrical protection by circuit breaker with a suitable dedic...

Страница 16: ...liance The cables used for the options and the power cord must be kept separate risk of interference using a collar inside the appliance just after the glands 1 5 1 Heating priority option This functi...

Страница 17: ...ater circulation to continuous operation 24 7 To maintain the temperature throughout the season run automatic circulation for the equivalent of the water temperature divided by two the longer this tim...

Страница 18: ...outlet adjustment valve optional An incorrect by pass setting may cause the heat pump to malfunction Check that the hydraulic connections are correctly tightened and that there are no leaks Check tha...

Страница 19: ...hes between HEATING and COOLING mode in order to keep the pool at the temperature setpoint 2 C Example When the temperature setpoint is 28 C if the water temperature rises to 30 C the heat pump will a...

Страница 20: ...onfirm the hours setting Once the hours have been confirmed the minutes begin to flash Set the minutes using the or keys Press to confirm the start time setting and proceed to setting the stop time in...

Страница 21: ...appliance you must cut the electricity supply as there is a risk of electric shock which may cause material damage serious injury or even death It is recommended that the appliance undergo general se...

Страница 22: ...ow below 8 C The appliance is smoking The machine has come to the end of the defrost cycle water has changed to gaseous state and passes through the grid If your heat pump is not in its defrost cycle...

Страница 23: ...erature too low Send the pump to the retailer for a detailed inspection E3 Faulty water flowmeter Flowmeter incorrectly positioned Re make the connections Insufficient water flow Increase the water fl...

Страница 24: ...l vous pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de...

Страница 25: ...ous pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d...

Страница 26: ...per l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d bit d eau Pow...

Страница 27: ...pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d bit...

Страница 28: ...pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d bit...

Страница 29: ...pecifications 5 1 I Description A PM40 B 1 5 PVC connectors C Anti vibration pads D Winterising cover Heating priority E Remote control kit F PAC NET cleaning product Included Available as an accessor...

Страница 30: ...e m h 2 3 3 4 6 5 8 6 9 7 10 7 11 7 11 9 13 19 Refrigerant type R32 R410A R32 R410A Refrigerant load kg 0 4 0 75 0 9 1 1 1 15 1 5 2 5 1 25 1 45 2 8 CO2 equivalent 0 27 teq CO2 0 5 teq CO2 0 60 teq CO2...

Страница 31: ...J K L J Rear PM40 MD1 MD2 MD3 MD4 MD5 MD7 MD8 TD7 TD8 TD12 F 798 958 1015 1015 1070 1070 1077 1070 1077 1077 G 293 360 370 370 416 416 446 416 446 446 H 511 581 621 621 708 708 958 708 958 1258 I 279...

Страница 32: ...23 49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d...

Отзывы: