background image

4

must be checked, as well as the absence of any traces of refrigerant.

• 

During the appliance's annual sealing test in accordance with applicable legislation, 

the  high  and  low  pressure  switches  must  be  checked  to  ensure  that  they  are 

securely fastened to the cooling circuit and that they cut off the electrical circuit 

when tripped.

• 

During maintenance work, ensure there are no traces of corrosion or oil around 

the cooling components.

• 

Before beginning work on the cooling circuit, stop the appliance and wait for a few 

minutes before fitting the temperature and pressure sensors. Some elements such 

as the compressor and piping may reach temperatures in excess of 100 °C and high 

pressures with the consequent risk of severe burns.

TROUBLESHOOTING

• 

All brazing must be carried out by qualified brazers.

• 

Replacement pipes must always be made of copper in compliance with standard 

NF EN 12735-1.

• 

Leak detection; pressure test:

 -

never use oxygen or dry air, risk of fire or explosion, 

 -

use  dry  nitrogen  or  the  mixture  of  nitrogen  and  refrigerant  indicated  on  the 

information plate, 

 -

the test pressure for both the high and low pressure circuits must not exceed 42 

bar in cases where the appliance is equipped with the optional pressure gauge.

• 

The high pressure circuit pipes are made of copper and have a diameter equal to or 

greater than 1’’5/8. A certificate as indicated in §2.1 in compliance with standard 

NF EN 10204 must be requested from the supplier and filed in the installation's 

technical file.

• 

Technical data relative to the safety requirements of the various applicable directives 

are indicated on the information plate. All this information must be recorded in the 

appliance's  installation  manual,  which  must  be  kept  in  its  technical  file:  model, 

code,  serial  number,  maximum  and  minimum  OT,  OP,  year  of  manufacture,  CE 

marking,  manufacturer’s  address,  refrigerant  and  weight,  electrical  parameters, 

thermo-dynamic and acoustic performance. 

MAINTENANCE:  WARNINGS  CONCERNING  APPLIANCES  CONTAINING  R32 

REFRIGERANT (models PM40 MD1, MD2, MD3, MD4, MD5, TD7 & TD8)

Area check

• 

Before starting work on systems containing flammable refrigerants, safety checks 

must be carried out to guarantee a minimal ignition risk.

Work procedure

• The work must be carried out according to a controlled procedure in order to 

reduce the risks of releasing a flammable gas or vapour while working.

General work area

• 

All maintenance staff and other personnel working in the surrounding area must 

be made aware of the work carried out. Work conducted in enclosed areas must 

be avoided.

Содержание PM40 Series

Страница 1: ...H0686400_REVA 2020 02 More documents on www zodiac com PM40 Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Страница 2: ......

Страница 3: ...nsible for their safety Children must be supervised to ensure that they do not play with the appliance This appliance must not be used by children under 8 or by adults whose reduced physical sensoryor...

Страница 4: ...t separation in all poles allowing for complete disconnection in the event of category III overvoltage the instructions shall specify that disconnection means must be integrated into the fixed wiring...

Страница 5: ...EU 517 2014 In order to comply with the applicable standards and regulations in terms of the environment and installation in particular French decree No 2015 1790 and or European regulation EU 517 201...

Страница 6: ...where the appliance is equipped with the optional pressure gauge The high pressure circuit pipes are made of copper and have a diameter equal to or greater than 1 5 8 A certificate as indicated in 2...

Страница 7: ...orming any maintenance task check that the area is open and well ventilated Suitable ventilation must be provided throughout the maintenance task to allow any refrigerant that could be released into t...

Страница 8: ...of the cable glands etc Make sure that the appliance is properly fixed Make sure that the seals or insulating materials are not deteriorated to the point that they no longer prevent a flammable atmos...

Страница 9: ...to take account of the product s flammability The following procedure must be followed remove the refrigerant purge the circuit with an inert gas optional for A2L drain optional for A2L purge with an...

Страница 10: ...ocated on the scales before starting recovery operations 7 Start the recovery unit and operate as per its instructions 8 Do not overfill the cylinders no more than 80 of the volume must be filled with...

Страница 11: ...have any doubts contact the manufacturer The recovered refrigerant must be sent to the refrigerant supplier in its recovery cylinder with a waste transfer note Do not mix different refrigerants in th...

Страница 12: ...to contact your retailer Write down your retailer s contact details to help you find them more easily and fill in the product information on the back of the manual your retailer will ask you for this...

Страница 13: ...llation on a roof a balcony or any other support Front Rear Anti vibration pads View of the appliance base from below for installing the anti vibration blocks The appliance must not be installed With...

Страница 14: ...o work on the appliance Water inlet valve By pass valve Water outlet valve Water inlet adjustment valve optional Water outlet adjustment valve optional Water treatment system To evacuate the condensat...

Страница 15: ...in the country where it is installed The appliance is provided for connection to a general power supply with a TT or TN S neutral regime Electrical protection by circuit breaker with a suitable dedic...

Страница 16: ...liance The cables used for the options and the power cord must be kept separate risk of interference using a collar inside the appliance just after the glands 1 5 1 Heating priority option This functi...

Страница 17: ...ater circulation to continuous operation 24 7 To maintain the temperature throughout the season run automatic circulation for the equivalent of the water temperature divided by two the longer this tim...

Страница 18: ...outlet adjustment valve optional An incorrect by pass setting may cause the heat pump to malfunction Check that the hydraulic connections are correctly tightened and that there are no leaks Check tha...

Страница 19: ...hes between HEATING and COOLING mode in order to keep the pool at the temperature setpoint 2 C Example When the temperature setpoint is 28 C if the water temperature rises to 30 C the heat pump will a...

Страница 20: ...onfirm the hours setting Once the hours have been confirmed the minutes begin to flash Set the minutes using the or keys Press to confirm the start time setting and proceed to setting the stop time in...

Страница 21: ...appliance you must cut the electricity supply as there is a risk of electric shock which may cause material damage serious injury or even death It is recommended that the appliance undergo general se...

Страница 22: ...ow below 8 C The appliance is smoking The machine has come to the end of the defrost cycle water has changed to gaseous state and passes through the grid If your heat pump is not in its defrost cycle...

Страница 23: ...erature too low Send the pump to the retailer for a detailed inspection E3 Faulty water flowmeter Flowmeter incorrectly positioned Re make the connections Insufficient water flow Increase the water fl...

Страница 24: ...l vous pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de...

Страница 25: ...ous pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d...

Страница 26: ...per l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d bit d eau Pow...

Страница 27: ...pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d bit...

Страница 28: ...pla t quiper l ext rieur A C contacteur appropri Water pump Pompe eau High Pressure switch Pressostat haute pression Low Pressure switch Pressostat basse pression Water Flow switch D tecteur de d bit...

Страница 29: ...pecifications 5 1 I Description A PM40 B 1 5 PVC connectors C Anti vibration pads D Winterising cover Heating priority E Remote control kit F PAC NET cleaning product Included Available as an accessor...

Страница 30: ...e m h 2 3 3 4 6 5 8 6 9 7 10 7 11 7 11 9 13 19 Refrigerant type R32 R410A R32 R410A Refrigerant load kg 0 4 0 75 0 9 1 1 1 15 1 5 2 5 1 25 1 45 2 8 CO2 equivalent 0 27 teq CO2 0 5 teq CO2 0 60 teq CO2...

Страница 31: ...J K L J Rear PM40 MD1 MD2 MD3 MD4 MD5 MD7 MD8 TD7 TD8 TD12 F 798 958 1015 1015 1070 1070 1077 1070 1077 1077 G 293 360 370 370 416 416 446 416 446 446 H 511 581 621 621 708 708 958 708 958 1258 I 279...

Страница 32: ...23 49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d...

Отзывы: