9.14
MODBUS Master
Addressing of the members that are activated via the MODBUS Master interface.
Addressing can be done automatically by a patented method. It is then no longer necessary to
address every single member manually in the network.
Alternatively, manual addressing is possible, for which separate components are required for setting
the individual member address.
Information
•
A
maximum of 32 devices
can be connected. The communication settings are pre-set to 19.2kbd,
8E1 and cannot be changed.
•
To ensure activation, the function of the digital input
“
D1
”
of the members is automatically set to
“
OFF
”
by the MODBUS Master. I.e. any programmed enable function for switching off the member
(by a potential-free contact) is no longer active.
Main menu
MODBUS Master
After addressing (manual or automatic), the devices are subsequently listed to the
“
MODBUS Master
”
menu group (
“
members MODBUS Master
”
).
MODBUS Master
Fan 1 (2A)
Fan 2 (2A)
Fan 3 (2A)
[P] Enter
[ESC] Info
9.14.1
Automatic addressing
•
The
fi
rst member (MODBUS address
1
) must be connected to the terminals 1A(1D+) and 1B (1D-),
additionally the
“
ID
”
connections must be connected (
installation / communication / addressing
members MODBUS Master interface).
•
The members are automatically addressed consecutively according to the installation.
•
In order to do the automatic addressing successfully, all the bus members to be addressed must be
connected with each other, applied to voltage and switched on.
The automatic addressing can only be done with compatible devices!
Main menu
MODBUS Master
Limits
Timer
Diagnostic
MODBUS Master
[P] Enter
[ESC] Info
MODBUS Master
1.
Press the P-key
to open the
“
MODBUS Master
”
.
2.
Press the P-key
to select automatic addressing.
3.
Press the P-key
to start automatic addressing.
Autoaddressing
[P] Enter
[ESC] Menu
MODBUS Master
Display while the automatic addressing is in progress.
Addressing
Found: 0
In progress
[P] Repeat
[ESC] Cancel
MODBUS Master
The found members count is displayed at the end of automatic addressing.
Press the
P-key
again to repeat the addressing.
Exit the menu with the Esc key combination
▼
+
▲
.
Addressing
Found: 5
Done
[P] Repeat
[ESC] Cancel
9.14.2
Manual addressing
The addressing is done manually by a separate hand held terminal or PC software, the corresponding
member count must be entered on the MODBUS Master.
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003