Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: depending on measuring range of sensor and
“
K factor
”
Factory setting: 530 m
3
/h
530 m
3
h
Pband
Setting
Min. Speed
Setting range: 0...
“
Max. Speed
”
Factory setting: 0 %
0 %
Min. Speed
Setting
Maximal Speed
Setting range: 100 %...
“
Min. Speed
”
Factory setting: 100 %
100 %
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...100 %
“
Min. Speed
”
...
“
Max. Speed
”
Factory setting: 100 %
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
100 %
Speed manual
Additional menu item for mode
5.02
with outside-temperature dependent target-setpoint
Outside-temperature dependent target-setpoint
Außentemperatur
P-min SA
[m
3
/h]
-15 °C
min. Temperatur
30 °C
T-Start
Sollwert 1
[m
3
/h]
Sollwert 2
[m
3
/h]
07.02.2007
v_sollwert_aussentemp_abhaengig_m3h.vsd
S1
Setpoint1
S2
Setpoint2
P-Min SA
Minimum air volume
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
to
“
Analog In
2
”
) when being operated as a air volume regu-
lation device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active Setpoint 1/2 is automatically
changed proportional to the measured outside
temperature (
Info:
“
Setpoint control
”
).
Setting
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
Setting range: 0.0..100.0 K
Factory setting: 30.0 K
30.0 K
T-Band SA
Setting
T-Start SA
Setpoint reducing will start below this outside temperature
Setting range: -10.0...40.0
°
C
Factory setting: 15.0
°
C
15.0
°
C
T-Start SA
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
47/114