Example 2: Temperature control in
“
Heating function
”
(Idealized principle diagram)
I
Min.
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
20 °C
S
10 K
R
10 °C
Max.
28.03.2013
v_tempcontrol_heat_cxe_master.vsd
80
70
60
50
40
30
20
10
90
A
n
a
lo
g
O
u
t
[V
]
1
2
3
4
5
6
7
8
9
1
0
M
O
D
B
U
S
O
u
t
[%
]
100
(Controller Setup:
“
Val > Set = n+
”
to
“
OFF
”
)
MODBUS Out:
speed setting over MODBUS
Analog Out:
speed setting over analog output 0 - 10 V
S
Setpoint
R
Pband
I
Actual value
9.2.4
Additionally for
2.03
(controller output 2 with function
|
6A
|
)
The 0 - 10 V output signal A2 can, e.g., be used for triggering a shutter or heating.
Setting
Offset AnalogOut
The target value for this output is the target value (Setpoint) for the ventilation
“
offset
”
setting.
Adjustment: range +/- 10,0 K relative to the active Setpoint.
Example for triggering a shutter servomotor:
At factory setting
“
0,0 K
”
= synchronous operation.
The analog output is factory set to increasing activation during increasing temperature.
Reprogramming to
“
Heating function
”
, i.e., increasing modulation during decreasing
temperature is possible (
IO Setup).
0.0 K
Offset AnalogOut
Setting
Pband AnalogOut
Pband AnalogOut = separately adjustable range of control (P-band) for 0 - 10 V output
Setting range: 0...200.0 K
Factory setting: 2.0 K
2.0 K
Pband AnalogOut
Setting
Min. AnalogOut
Min. AnalogOut = Minimal output voltage
Setting range: 0...100 % = 0 - 10 V
Factory setting: 0 %
0 %
Min. AnalogOut
Setting
Max. AnalogOut
Max. AnalogOut = Maximal output voltage
Setting range: 100...0 % = 10 - 0 V
Factory setting: 100 %
100 %
Max. AnalogOut
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
35/114