9.9.10
Display text for external message
Controller Setup
Alternatively to the
“
External Error
”
display when an external message occurs (
IO
Setup / Digital Inputs
“
D1
”
/
“
D2
”
the following error texts can be programmed:
•
EC Motors
•
Filter
•
Frost protection
•
Adiabatik
•
Firealarm
•
Pressure switch
•
Gas alarm
•
Water alarm
•
RCD
External error
External message
RCD
Residual-current-operated protective device
9.9.11
Offset control signal
Controller Setup
Offset control sig. 1
If required, the characteristic of the control signal for control circuit 1 can be adjusted.
To activate this function, re-program the output with function
|
2A
|
to function
|
14A
|
.
IO Setup.
Setting range: 0 - 50 %
Factory setting: 0 % (characteristic curve unchanged)
0 %
Offset control sig. 1
13.03.2015
v_offset_controlsig_cxe.vsd
1
2
3
4
5
6
7
8
9
10
Analog In 1
2
4
6
8
10
12
14
16
18
20
0...10 V
0...20 mA
10
20
30
40
50
60
70
80
90
100 0...100 % PWM
0
0
0
Analog Out [V]
A1 Offset (2A) = 0 %
A1 Offset (14A) = 50 %
A1 Offset (14A) = -10 %
80
70
60
50
40
30
20
10
90
A
n
a
lo
g
O
u
t
[V
]
1
2
3
4
5
6
7
8
9
1
0
M
O
D
B
U
S
O
u
t
[%
]
100
Operating Instructions
UNIcon MODBUS Master
Programming
L-BAL-E207-GB 1723 Index 003
Part.-No.
62/114